Laserfiche WebLink
PRO"ALFOR <br />On -Call Engineering Design Services <br />PFAS Treatment Systems <br />Existing Condition 2454 256 285 <br />(No PFAS) <br />Proposed IX Treatment with Clean 2,454 302 328 <br />,Filters <br />proposed IX Treatment with Dir#y 2,454 317 343 <br />Filters <br />A system curve for Well 26 with PEAS treatment is presented in Figure 1. The existing well pump curve is not <br />provided at this time, therefore a generic curve is included to indicate a pump curve that would be capable of <br />incorporating treatment. During the design process Tetra Tech will evaluate all of the actual existing well pump <br />curves against the calculated new system curve to determine the well pump's ability to meet the new system <br />pressure requirements with PFAS treatment. The maximum flow rate the pump will operate at with the new <br />treatment will be presented, and if unacceptable recommendations made for modifications such as adding <br />bowls, changing motor size, or replacing the well pump entirely. <br />ON 11 <br />-�faa. �.n� Sc..l I�.ri Sv.,e� irr•r. — Mi • �•.�.I or�rwr. Sy.rem IIrry --11 • Ile , I •-w —[ 14i L v Mr L�INf <br />a 500 Iv 1500 z000 25m Soon -5,X1 <br />now Igp-) <br />,5 <br />-------------------------- - ------------ ------ - <br />20 <br />s <br />n <br />O 2 4 6 B 10 12 14 l5 16 20 22 74 26 29 30 32 3A 36 <br />Months oS Ope 4tj0 <br />• Influent lead — W L.N <br />Figure 1. Preliminary system <br />curve for Well 26 and <br />example pump curve. <br />note: actual pump curve not <br />available, shown is an example <br />for demonstrative purposes - <br />Figure 2. Example lead lag <br />model for use to establish <br />increased monitoring and <br />resin change -out <br />frequency requirements. <br />TETRA TECH Page 111 <br />