| 
								    Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />floor/ceiling assemblies, and an added requirement dictates that the Impact Insulation Class (IIC) rating of the 
<br />floor/ceiling assembly is a minimum laboratory rating of IIC 50. 
<br />Further details regarding the evaluation of common wall and floor/ceiling assemblies are provided in Appendix 
<br />E. The limitations and general recommendations listed in this section should also be taken into account in the 
<br />construction of this building. Some assembly ratings were obtained from the California Department of Health 
<br />Services Office of Noise Control Catalog of STC and IIC Ratings for Wall and Floor/Ceiling Assemblies (see 
<br />reference), hereafter referred to as "Catalog." 
<br />Wall Assemblies 
<br />Wood -Framed One Hour -Bated Wall at Corridor (2/AD 22) 
<br />In some locations where residential units are located adjacent to corridors, the following assembly is proposed: 
<br />• Single layer of 5/8-inch-thick Type X gypsum board 
<br />• 2-inch by 4-inch wooden studs, staggered on a 6-inch (minimum) bottom plate, spaced at 16 inches 
<br />on -center 
<br />• Fiberglass batt insulation in each cavity 
<br />• Single layer of 5/8-inch-thick Type X gypsum board 
<br />A laboratory STC test of this assembly was conducted by Owens Corning (Catalog section number 1.2.3.1.5.3) 
<br />and achieved an STC rating of 46, which does not meet the California Building Code requirement for a 
<br />minimum STC rating of 50. Therefore, the wood -framed one -hour corridor wall should be improved as 
<br />follows: 
<br />Impmved Wood -Framed One -Hour -Rated Wall at Corridor (2/AD-22) 
<br />• Double layer of 5/8-inch-thick Type X gypsum board (inner layer can be replaced with 
<br />plywood where required for shear) 
<br />• 2-inch by 4-inch wooden studs, staggered on a 6-inch (minimum) bottom plate, spaced at 16 
<br />inches on -center 
<br />• Fiberglass batt insulation in each cavity 
<br />• Single layer of 5/8-inch-thick Type X gypsum board 
<br />A laboratory test was performed by the National Research Council of Canada (test number T1-93- 
<br />226) for this wall assembly and achieved an STC rating of 52 and is therefore expected to meet the 
<br />California Building Code requirement for a minimum STC rating of 50. 
<br />Wood -Framed One -Hour -Rated Pary Wall (3/AD 22) 
<br />In some locations where residential units are located adjacent to one another, the following assembly is 
<br />proposed: 
<br />• Single layer of 5/8-inch thick Type X gypsum board 
<br />• Double row of 2-inch by 4-inch wooden studs, spaced at 16 inches on -center, separated by 1-inch gap 
<br />• Fiberglass batt insulation in each cavity 
<br />• Single layer of 5/8-inch thick Type X gypsum board 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 12 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />A laboratory test was performed by Riverbank Acoustical Labs (Catalog Section 1.2.4.1.5.4) for this wall 
<br />assembly. The tested assembly achieved an STC rating of 57 and is therefore expected to meet the California 
<br />Building Code requirement for a minimum STC rating of 50. The addition of layers of gypsum board on either 
<br />side of the assembly is expected to increase the overall rating; therefore, where a double layer of gypsum board 
<br />is used on one or both sides of the parry wall (such as with the two-hour rated party wall [7/AD-221), the STC 
<br />rating of the assembly would exceed STC 57. 
<br />Metal -Framed One -Hour -Rated Par 
<br />y Wall (11 /AD 22) 
<br />In some locations where residential units are located adjacent to one another, the following assembly is 
<br />proposed: 
<br />• Double layer of 5/8-inch thick Type X gypsum board 
<br />• Double row of 3-5/8-inch studs, spaced at 16 inches on -center, separated by 1-inch gap 
<br />• Fiberglass batt insulation in each cavity 
<br />• Single layer of 5/8-inch thick Type X gypsum board 
<br />No specific sound test was available for this exact configuration; however, the above assembly was evaluated 
<br />using INSUL, and was shown to have an STC rating of 65, which meets the California Building Code 
<br />requirement for a minimum STC rating of 50. The addition of layers of gypsum board on either side of the 
<br />assembly is expected to increase the overall rating; therefore, where a double layer of gypsum board is used on 
<br />both sides of the parry wall (such as with the two -hour -rated parry wall [15/AD-22]), the STC rating of the 
<br />assembly would exceed STC 65. 
<br />Three -Hour -Rated Fire Wall (1 /AD-25) 
<br />The three-hour fire wall is proposed to be constructed as follows: 
<br />• Single layer of 5/8-inch-thick Type X gypsum board 
<br />• Single layer of plywood sheathing (where occurs) 
<br />• Single row of 2-inch by 4-inch wooden studs, spaced at 16 inches on -center 
<br />• Air gap, with fiberglass insulation in the air cavity 
<br />• Single layer of 1-inch-thick Type X gypsum board 
<br />• Single row of 2-1/2-inch CH studs, spaced at 16 inches on -center 
<br />• Triple layer of 5/8-inch-thick Type X gypsum board 
<br />• Air gap, with fiberglass insulation in the air cavity 
<br />• Single row of 2-inch by 4-inch wooden studs, spaced at 16 inches on -center 
<br />• Single layer of 5/8-inch-thick Type X gypsum board 
<br />No specific sound test was available for this exact configuration; however, the interior three -hour -rated core 
<br />stud with one side of the wood -framed furring wall assembly was evaluated using INSUL and was shown to 
<br />have an STC rating of 66. Due to the complexity of the overall assembly, the entire assembly could not be 
<br />evaluated using INSUL, and therefore the contribution that the other wood -framed furring wall assembly would 
<br />have on the STC rating of the overall assembly could not be evaluated. However, the addition of the wood - 
<br />framed furring walls is not expected to increase the STC rating of the assembly significantly, and therefore, a 
<br />conservative STC rating of the above assembly is STC 66. This assembly is expected to comply with the 
<br />minimum STC requirements of the California Building Code as currently designed. 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 13 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />5.2 Interior 
<br />5.2.1 Transportation Noise Sources 
<br />DWellinLr Units 
<br />The State of California and the City of Santa Ana require buildings to be designed in order to attenuate, control, 
<br />and maintain interior noise levels not greater than 45 CNEL in habitable space, as formulated in the City of 
<br />Santa Ana. Noise Element to the General Plan and the California Building Code, Section 1206.4. According to 
<br />the U.S. EPA (see reference), current exterior building construction is generally expected to achieve at least 15 
<br />decibels of exterior -to -interior noise attenuation with windows opened. Therefore, proposed project building 
<br />structures exposed to exterior noise levels greater than 60 CNEL could be subject to interior noise levels 
<br />exceeding the 45 CNEL noise limit for residential habitable space. As exterior noise levels at most building 
<br />facades exceed 60 CNEL, an exterior -to -interior analysis was performed for representative units to determine 
<br />design considerations required to maintain compliant interior noise levels. 
<br />The typical exterior wall assembly is proposed to be constructed as a 2-inch by 6-inch wood -framed assembly 
<br />with stucco on the exterior, insulation in the cavity, and one layer of 5/8-inch thick Type X gypsum board on 
<br />the interior. The typical exterior wall assembly was evaluated using INSUL and was shown to achieve an STC 
<br />rating of 38. Please refer to Appendix E for additional information. 
<br />The results of the exterior -to -interior noise analysis for interior habitable spaces are shown in Table 7, with 
<br />acoustical recommendations made therein. For more information, please refer to Appendix F: Exterior -to - 
<br />Interior Noise Analysis. 
<br />Table 7. Interior Noise Levels of Representative Units 
<br />Room Type 
<br />Maximum Exterior 
<br />Facade Impact 
<br />(CNEL) 
<br />STC Rating 
<br />for Glazing 
<br />Interior Noise Level (CNEL) 
<br />Windows/ 
<br />Doors Open 
<br />Windows/ 
<br />Doors Closed 
<br />Living / Kitchen / Dining 
<br />72 
<br />28 
<br />60 
<br />42 
<br />Bedroom 
<br />72 
<br />28 
<br />61 
<br />41 
<br />As shown above, with proposed exterior walls and exterior glazing with a minimum STC rating of 28, interior 
<br />noise levels will remain below 45 CNEL in all habitable space with windows and exterior doors closed. The 
<br />sound rating of exterior glazing should be confirmed with the manufacturer prior to installation to confirm 
<br />these STC rating requirements will be met. 
<br />In instances where interior habitable space is exposed to noise levels greater than 45 CNEL with windows in 
<br />the open position, appropriate means of air circulation and provision of fresh air must be present to allow 
<br />windows to remain closed for extended intervals of time so that acceptable levels of noise can be maintained 
<br />on the interior. As exterior noise levels are expected to exceed limits with windows and doors open at all units, 
<br />mechanical ventilation will be required in all units. The proposed mechanical ventilation system shall meet the 
<br />criteria of the California Mechanical Code, including the capability to provide appropriate ventilation rates. The 
<br />ventilation system shall not compromise the sound insulation capability of the exterior wall or be dependent 
<br />on ventilation through windows. 
<br />Exterior door installation should include all-around weather -tight door stop seals and an improved threshold 
<br />closure system. The additional hardware will improve the doors' overall sound reduction properties. The 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 
<br />Page 10 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />transmission loss (TL) of an exterior door without weather -tight seals is largely a factor of sound leakage, 
<br />particularly at the bottom of the door if excessive clearance is allowed for air transfer. By equipping exterior 
<br />doors with all-around weather -tight seals and an airtight threshold closure at the bottom, a loss of up to 10 STC 
<br />points can be prevented. 
<br />Additionally, it is imperative to seal and caulk between the rough opening and the finished door frame for all 
<br />doors by applying an acoustically resilient, non -skinning, butyl caulking compound. Sealant application should 
<br />be as generous as needed to ensure effective sound barrier isolation. The same recommendation applies to any 
<br />other penetrations, cracks, or gaps through the assembly. The OSI SC175 and the Pecora AC-20 FTR acoustic 
<br />sound sealants are products specifically designed for this purpose. For additional information on these 
<br />products, please refer to Appendix G: Recommended Products. 
<br />The proposed habitable spaces were analyzed for interior noise impacts. With the proposed exterior walls and 
<br />exterior glazing with a minimum STC rating of 28 in place, interior noise levels will remain below 45 CNEL in 
<br />all habitable space with windows and exterior doors closed. As exterior noise levels are expected to exceed 
<br />limits with windows and doors open in all units, mechanical ventilation will be required for all units. With these 
<br />project design features in place, all interior residential space will comply with City of Santa Ana and California 
<br />Building Code noise requirements. 
<br />Nonresidential Snaces 
<br />CALGreen also requires buildings to be designed in order to attenuate, control, and maintain interior noise 
<br />levels not greater than 50 dBA LEQ peak hour in nonresidential space. For the purposes of this analysis, dBA 
<br />LEQ peak hour is considered equivalent to CNEL. According to the U.S. EPA (see reference), current exterior 
<br />building construction is generally expected to achieve at least 15 decibels of exterior -to -interior noise 
<br />attenuation with windows opened. Therefore, proposed project building structures exposed to exterior noise 
<br />levels greater than 65 CNEL could be subject to interior noise levels exceeding the 50 CNEL noise limit for 
<br />nonresidential habitable space. 
<br />The typical exterior wall assembly was evaluated as detailed above; proposed windows were evaluated as 1- 
<br />inch-thick dual -glazed windows, and doors were evaluated as 1/4-inch single pane glass doors for a conservative 
<br />analysis of standard commercial glazing. Please refer to Appendix E for additional information. 
<br />The results of the exterior -to -interior noise analysis for worst -case nonresidential spaces are shown in Table 8. 
<br />For more information, please refer to Appendix F: Exterior -to -Interior Noise Analysis. 
<br />Table 8. Interior Noise Levels of Nonresidential Space 
<br />Room 
<br />Maximum Exterior Facade 
<br />Interior Noise Level 
<br />Impact (CNEL) 
<br />(CNEL) 
<br />Worst -Case Nonresidential Space 
<br />72 
<br />41 
<br />As shown above, with the anticipated exterior wall assembly and standard commercial gJazing, interior noise 
<br />levels in nonresidential space will comply with CALGreen requirements. 
<br />5.2.2 Unit -to -Unit Noise Transmission 
<br />Another source of noise that may affect residential units in multi -family buildings is unit -to -unit noise 
<br />transmission. The California State Building Code Section 1206 requires that the Sound Transmission Class 
<br />(STC) rating of common wall assemblies separating residential units or separating residential units from 
<br />common areas have a minimum laboratory rating of STC 50. The same STC requirement applies for 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 11 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />5.0 Impacts and Mitigation 
<br />5.1 Exterior 
<br />5.1.1 Outdoor Use Areas 
<br />As per the City of Santa Ana Noise Element to the General Plan, exterior noise levels at common outdoor use 
<br />areas should not exceed 65 CNEL for residential areas. The proposed common outdoor use areas on site 
<br />include courtyards at both buildings and a roof deck on the seventh floor of Building A. 
<br />Common outdoor use areas were evaluated to determine if noise levels exceed 65 CNEL. Future combined 
<br />traffic and rail noise levels for the common outdoor use area are shown in Table 4, and take into account the 
<br />shielding provided by the proposed buildings on site. Receivers were placed at a height of 3.5 feet above grade, 
<br />to approximate the height of a seated person. The receiver locations are shown in Figure 7. 
<br />Table 4. Future Exterior Noise Levels at Common Outdoor Use Areas 
<br />Receiver 
<br />Location 
<br />Noise Limit 
<br />(CNEL) 
<br />Exterior Noise 
<br />Level (CNEL) 
<br />OUl 
<br />Building A — 7th Floor Roof Deck 
<br />65 
<br />56 
<br />OU2 
<br />Building A — 3rd Floor Courtyard/Pool Deck 
<br />65 
<br />53 
<br />OU3 
<br />Building B — Courtyard 
<br />65 
<br />68 
<br />OU4 
<br />Building B — Dog Park 
<br />65 
<br />63 
<br />As shown in Table 4, exterior noise levels at the common outdoor use areas are expected to exceed the noise 
<br />limit of 65 CNEL at the Building B courtyard as currently designed. Therefore, a 4-foot barrier wall was 
<br />incorporated along the southern boundary of the Building B courtyard to reduce noise levels at outdoor use 
<br />areas. Please refer to Table 5 for mitigated noise levels at outdoor use areas, and Figure 7 for barrier locations. 
<br />Table 5. Future Exterior Noise Levels at Common Outdoor Use Areas — with 4-foot Barrier 
<br />Receiver 
<br />Location 
<br />Noise Limit 
<br />Exterior Noise 
<br />(CNEL) 
<br />Level (CNEL) 
<br />OU3 
<br />Building B — Courtyard 
<br />65 
<br />65 
<br />As shown in Table 5, with the 4-foot sound barrier in place along the southern boundary of the Building B 
<br />courtyard, exterior noise levels at the common outdoor use areas are expected to meet the exterior noise limit 
<br />of 65 CNEL. A sound attenuation wall should be solid and constructed of masonry, wood, plastic, fiberglass, 
<br />steel, or a combination of those materials, with no cracks or gaps, through or below the wall. Any seams or 
<br />cracks must be filled or caulked. If wood is used, it can be tongue and groove and must be at least 7/8-inch 
<br />thick or have a surface density of at least 3-1/2 pounds per square foot. Where architectural or aesthetic factors 
<br />allow, glass or clear plastic may be used on the upper portion, if it is desirable to preserve a view. 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 
<br />5.1.2 Building Facades 
<br />Page 8 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />Future combined traffic and rail noise impacts were calculated for all project building facades. Future noise 
<br />levels at the building facades are expected to range from 47 CNEL at the courtyard of Building A to 72 CNEL 
<br />at the south facade of Building B. Calculation results are shown in Table 6, and receiver locations are shown 
<br />graphically in Figure 8. 
<br />Table 6. Future Exterior Noise Levels at Building Facades 
<br />Building 
<br />Receiver 
<br />Direction 
<br />Future Exterior Noise Level (CNEL) 
<br />Floor 1 
<br />Floor 2 
<br />Floor 3 
<br />Floor 4 
<br />Floor 5 
<br />Floor 6 
<br />Floor 7 
<br />F1 
<br />West 
<br />62 
<br />62 
<br />63 
<br />63 
<br />62 
<br />62 
<br />62 
<br />F2 
<br />West 
<br />70 
<br />70 
<br />69 
<br />68 
<br />67 
<br />67 
<br />66 
<br />F3 
<br />South 
<br />72 
<br />71 
<br />70 
<br />69 
<br />68 
<br />68 
<br />67 
<br />F4 
<br />South 
<br />72 
<br />71 
<br />70 
<br />-- 
<br />-- 
<br />-- 
<br />-- 
<br />F5 
<br />South 
<br />72 
<br />71 
<br />70 
<br />69 
<br />68 
<br />68 
<br />67 
<br />A 
<br />F6 
<br />East 
<br />68 
<br />68 
<br />68 
<br />67 
<br />66 
<br />66 
<br />65 
<br />F7 
<br />East 
<br />65 
<br />65 
<br />65 
<br />65 
<br />64 
<br />64 
<br />63 
<br />F8 
<br />East 
<br />66 
<br />66 
<br />65 
<br />65 
<br />64 
<br />-- 
<br />-- 
<br />F9 
<br />North 
<br />69 
<br />68 
<br />67 
<br />66 
<br />65 
<br />-- 
<br />-- 
<br />F10 
<br />Courtyard 
<br />-- 
<br />-- 
<br />62 
<br />65 
<br />64 
<br />64 
<br />63 
<br />F11 
<br />Courtyard 
<br />-- 
<br />-- 
<br />47 
<br />52 
<br />59 
<br />59 
<br />59 
<br />F12 
<br />Courtyard 
<br />-- 
<br />-- 
<br />62 
<br />65 
<br />64 
<br />64 
<br />63 
<br />F13 
<br />North 
<br />68 
<br />68 
<br />67 
<br />67 
<br />66 
<br />-- 
<br />-- 
<br />F14 
<br />West 
<br />67 
<br />67 
<br />67 
<br />66 
<br />66 
<br />-- 
<br />-- 
<br />F15 
<br />West 
<br />65 
<br />66 
<br />66 
<br />65 
<br />65 
<br />-- 
<br />-- 
<br />F16 
<br />West 
<br />64 
<br />65 
<br />65 
<br />65 
<br />65 
<br />-- 
<br />-- 
<br />F17 
<br />West 
<br />70 
<br />69 
<br />69 
<br />68 
<br />68 
<br />-- 
<br />-- 
<br />B 
<br />F18 
<br />South 
<br />72 
<br />71 
<br />70 
<br />69 
<br />68 
<br />-- 
<br />-- 
<br />F19 
<br />Courtyard 
<br />69 
<br />69 
<br />68 
<br />68 
<br />67 
<br />-- 
<br />-- 
<br />F20 
<br />Courtyard 
<br />65 
<br />66 
<br />66 
<br />66 
<br />65 
<br />-- 
<br />-- 
<br />F21 
<br />Courtyard 
<br />69 
<br />69 
<br />68 
<br />68 
<br />67 
<br />-- 
<br />-- 
<br />F22 
<br />South 
<br />72 
<br />71 
<br />70 
<br />69 
<br />68 
<br />-- 
<br />-- 
<br />F23 
<br />East 
<br />68 
<br />68 
<br />68 
<br />68 
<br />67 
<br />-- 
<br />-- 
<br />F24 
<br />East 
<br />64 
<br />65 
<br />65 
<br />65 
<br />65 
<br />-- 
<br />-- 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 9 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />4.1.3 Roadway Noise Calculation 
<br />The Traffic Noise Model (TNM) calculation protocol in CadnaA Version 2022 (based on the methodology 
<br />used in TNM Version 2.5, released in February 2004 by the U.S. Department of Transportation) was used for 
<br />all traffic modeling in the preparation of this report. Using the TNM protocol, the CNEL is calculated as 9.2% 
<br />of the ADT for surrounding roadways, based on the studies made by Wyle Laboratories (see reference). Future 
<br />CNEL is calculated for desired receptor locations using future road alignment, elevations, lane configurations, 
<br />projected traffic volumes, estimated truck mixes, and vehicle speeds. Noise attenuation methods may be 
<br />analyzed, tested, and planned with TNM, as required. 
<br />In order to determine the estimated traffic volumes of roadways during the traffic noise measurement made on 
<br />site for model calibration, the approximate percentage of the Average Daily Trips (ADT) value for the time 
<br />period in which the measurement is made is incorporated into the traffic model. These percentages were 
<br />established in a study performed by Katz-Okitsu and Associates, Traffic Engineers (see reference). For 
<br />purposes of calibrating the CadnaA TNM, 5.3% of the ADT values for the current environment were used in 
<br />calculations (for roadways that were not manually counted) to account for traffic between the hours of 10 a.m. 
<br />and 11 a.m. in the vicinity of the project site. 
<br />4.1.4 Exterior -to -Interior Noise Analysis 
<br />The State of California and the City of Santa Ana require buildings to be designed in order to attenuate, control, 
<br />and maintain average interior noise levels not greater than 45 CNEL in residential space, as formulated in the 
<br />California Building Code, Section 1206.4 and the City of Santa Ana Noise Element to the General Plan. 
<br />Contemporary exterior building construction is expected to achieve at least 15 decibels of exterior -to -interior 
<br />noise attenuation with windows opened, according to the U.S. Environmental Protection Agency Office of 
<br />Noise Abatement and Control (see reference). As a result, exterior noise levels of more than 60 CNEL often 
<br />result in interior conditions that fail to meet the 45 CNEL requirements for habitable space. 
<br />Analysis for the interior noise levels requires consideration of: 
<br />• Number of unique assemblies in the wall (doors, window/wall mount air conditioners, sliding glass 
<br />doors, and windows) 
<br />• Size, number of units, and sound transmission data for each assembly type 
<br />• Length of sound impacted wall(s) 
<br />• Depth of sound impacted room 
<br />• Height of exterior wall of sound impacted room 
<br />• Exterior noise level at wall assembly or assemblies of sound impacted room 
<br />The Composite Sound Transmission data is developed for the exterior wall(s), and the calculated noise exposure 
<br />is converted to octave band sound pressure levels (SPL) for a typical traffic type noise. The reduction in room 
<br />noise due to absorption is calculated and subtracted from the interior octave noise levels, and the octave band 
<br />noise levels are logarithmically summed to yield the overall interior room noise level. When interior noise levels 
<br />exceed 45 CNEL, the noise reduction achieved by each element is reviewed to determine which changes will 
<br />achieve the most cost-effective compliance. Windows are usually the first to be reviewed, followed by exterior 
<br />doors, and then exterior walls. 
<br />Modeling of wall assemblies is accomplished using INSUL Version 9.0, which is a model -based computer 
<br />program, developed by Marshall Day Acoustics for predicting the sound insulation of walls, floors, ceilings, 
<br />and windows. It is acoustically based on theoretical models that require only minimal material information that 
<br />can make reasonable estimates of the sound transmission loss (TL) and STC for use in sound insulation 
<br />calculations, such as the design of common parry walls and multiple family floor -ceiling assemblies, etc. INSUL 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 6 
<br />Eilar Associates, Inc. 
<br />Acoustical and Environmental Consulting Services 
<br />can be used to quickly evaluate new materials or systems or investigate the effects of changes to existing designs. 
<br />It models individual materials using the simple mass law and coincidence frequency approach and can model 
<br />more complex assembly partitions, as well. It has evolved over several versions into an easy to use tool and has 
<br />refined the theoretical models by continued comparison with laboratory tests to provide acceptable accuracy 
<br />for a wide range of constructions. INSUL model performance comparisons with laboratory test data show that 
<br />the model generally predicts the performance of a given assembly within 3 STC points. IIC predictions are 
<br />generally made based on laboratory tests from a number of resources, including third -party test data provided 
<br />by product manufacturers and National Research Council of Canada test results. 
<br />4.1.5 Sound Transmission Class (STC) and Impact Insulation Class (IIC) Ratings 
<br />Sound Transmission Class (STC) is a single number rating calculated in accordance with ASTM E413, using 
<br />third -octave values of sound transmission loss. It provides an estimate of the sound performance of a partition, 
<br />window, or door in sound insulation problems. Likewise, Impact Insulation Class (IIC) is a single number 
<br />rating calculated in accordance with ASTM E989 that is used to describe the transmission of impact noise 
<br />through floor/ceiling assemblies, caused primarily by footsteps from one space to another. 
<br />Modeling of wall and floor/ceiling assemblies is accomplished using INSUL Version 9.0, which is a model - 
<br />based computer program, developed by Marshall Day Acoustics for predicting the sound insulation of walls, 
<br />floors, ceilings, and windows. It is acoustically based on theoretical models that require only minimal material 
<br />information that can make reasonable estimates of the sound transmission loss (TL), STC, and IIC for use in 
<br />sound insulation calculations, such as the design of common party walls and multiple family floor -ceiling 
<br />assemblies, etc. INSUL can be used to quickly evaluate new materials or systems or investigate the effects of 
<br />changes to existing designs. It models individual materials using the simple mass law and coincidence frequency 
<br />approach and can model more complex assembly partitions, as well. It has evolved over several versions into 
<br />an easy to use tool and has refined the theoretical models by continued comparison with laboratory tests to 
<br />provide acceptable accuracy for a wide range of constructions. INSUL model performance comparisons with 
<br />laboratory test data show that the model generally predicts the performance of a given assembly within 3 STC 
<br />points. IIC predictions are generally made based on laboratory tests from a number of resources, including 
<br />third -party test data provided by product manufacturers and National Research Council of Canada test results. 
<br />4.2 Measurement Equipment 
<br />Some or all of the following equipment was used at the site to measure existing noise levels: 
<br />• Larson Davis Model LxT Type 1 Sound Level Meter, Serial # 4085 
<br />• Larson Davis Model CAL200 Type 1 Calibrator, Serial # 16455 
<br />The sound level meter was field -calibrated immediately prior to the noise measurement and checked afterward 
<br />to ensure accuracy. All sound level measurements presented in this report, in accordance with the regulations, 
<br />were conducted using a sound level meter that conforms to the American National Standards Institute 
<br />specifications for sound level meters (ANSI S1.4). All instruments are maintained with National Institute of 
<br />Standards and Technology (NISI) traceable calibration, per the manufacturers' standards. 
<br />Acoustical Analysis Report for 4th and Mortimer • Job # S220404 • July 18, 2022 Page 7 
<br />Architecture + Planning 
<br />17911 Von Karman Ave. 
<br />Suite 200 
<br />Irvine, CA 92614 
<br />ktgy.com 
<br />949.851.2133 
<br />KTGY Project No: 2017-0934 
<br />Project Contact: Debbie Holland 
<br />Email: dholland@ktgy.com 
<br />Principal: Wil Wong 
<br />Project Designer: D. Schoolmeester 
<br />Project Director: Debbie Holland 
<br />Developer 
<br />ED QAK 
<br />INVES'I'MEN'I'S 
<br />4199 CAMPUS DRIVE 
<br />IRVINE, CA 92612 
<br />PHONE NO. (714) 342-2502 
<br />TF 
<br />Z 
<br />Q 
<br />2 
<br />H 
<br />r 
<br />O 
<br />N 
<br />Cn 
<br />Q 
<br />U 
<br />Q 
<br />Z 
<br />Q 
<br />Q 
<br />Z 
<br />Q 
<br />LU 
<br />w 
<br />LO 
<br />T_ 
<br />LO 
<br />06 
<br />LO 
<br />No. Date Description H 
<br />v , 
<br />U 
<br />w 
<br />2 
<br />U 
<br />Z 
<br />Q 
<br />J 
<br />It is the clients responsibility prior to or during construction to notify the architect in writing 
<br />n 
<br />of any perceived errors or omissions in the plans and specifications of which a contractor 
<br />thoroughly knowledgeable with the building codes and methods of construction should 
<br />reasonably be aware. Written instructions addressing such perceived errors or omissions 
<br />shall be received from the architect prior to the client or clients subcontractors proceeding 
<br />' ^ 
<br />with the work. The client will be responsible for any defects in construction if these 
<br />procedures are not followed. 
<br />v, 
<br />SEp ARCM 
<br />ILL 
<br />CV 
<br />No. C29795 
<br />C ) 
<br />RENEWAL DATE 
<br />AUGUST 31, 2023 
<br />qTF OF 
<br />� 
<br />CA\-�F��� 
<br />License Stamp 
<br />o 
<br />EXTERIOR 
<br />ACOUSTICAL 
<br />ANALYSIS REPORT 
<br />COPYRIGHT 7 
<br />AO-92 
<br />
								 |