Laserfiche WebLink
<br />. <br /> <br />. <br /> <br />APPENDIX C <br /> <br />LOCATION: <br /> <br />Santa Ana City Hall <br /> <br />~ Kohler 600-Watt Standby Generator Set Model 600ROZD4 <br />sIn 0707170 <br /> <br />ANNUAL MAINTENANCE FOR KOHLER 600-WATT STANDBY <br />GENERATOR SET <br /> <br />SCHEDULED OIL SAMP ING <br /> <br />1. Complete chemical analysis of oil. <br /> <br />ENGINE OIL AND FILTERS <br /> <br />1. Drainl replace oil in crankcase. <br />2. Replace oil filters and inspect used filters for foreign matter. <br /> <br />FUEL SYSTEM <br /> <br />1.Drain water and sediment from tank. <br />2.Change fuel filters. <br />3.Test fuel for water content and algae formation. <br />4. Inspect all fuel lines. <br /> <br />COOLING SYSTEM <br /> <br />1. Complete chemical analysis of coolant. <br />2. Replace thermostat(s). <br />3. Refill cooling system with coolant and conditioner. <br />4. Clean cooling system radiator of dirt and debris. <br />5. Drain, clean and flush cooling system. <br />6. Inspect and clean radiators. <br /> <br />EXHAUST SYSTEM <br /> <br />1. Check for leaks. <br />2. Inspect and clean any build up. <br /> <br />WordIRFQ -Emergency Generators/Fire Pump <br /> <br />03-08-02 <br />