Laserfiche WebLink
(a) Subsection 907.2.413 of the California Fire Code is amended as follows: <br />907.2.4'13 High-rise buildings and Group I-2 occupancies. <br />Buildings with a floor used for human occupancy located more than 55 <br />feet above the lowest level of fire department vehicle access shall be <br />provided with an automatic fire alarm system and an emergency <br />voice/alarm communication system in accordance with 907.2??z6.2.2. <br />Exceptions: <br />1. Airport traffic control towers in accordance with Section <br />907.2.22 and Section 412 of the California Building Code. <br />2. Open parking garages in accordance with Section 406.3 of <br />the California Building Code. <br />? °i?'^'?^^° ^*~ ^d,?ans3?in 6reap 1! a in asserdanse <br />with a92 1 7 ^f +he r-.-,i:c..?.-.:... Q -?,a- ??? <br />43. Low-hazard special occupancies in accordance with Section <br />503.1 .1 of the California Building Code. <br />5 Bu_?I.-1:.+9^ -•ith an essdpans?in-?rE*d? H 1, H 2 arT-o-.,? <br />(b) Subsection 907.9-X7.3.2 of the California Fire Code is amended as <br />follows: <br />907.97.3.2 High-rise buildings and Group I-2 occupancies. <br />In buildings with a floor used for human occupancy that is located more <br />than 55 feet above the lowest level of fire department vehicle access, a <br />separate zone by floor shall be provided for all of the following types of <br />alarm-initiating devices where provided: <br />1 . Smoke detectors. <br />2. Sprinkler water-flow devices. <br />3. Manual fire alarm boxes. <br />4. Other approved types of automatic fire detection or <br />suppression systems. <br />Ordinance No. NS-XXXX <br />7C /? _?2 Page 44 of 50