Sec. 8 -105. r°°°�^�^� High -rise buildings (Section 907.6.3.2). <br />Section 907.6.3.2 is amended to read as a follows: <br />907 6 3 2 High -rise buildings High -rise buildings having occupied floors <br />located more than 55 feet above the lowest level of fire department vehicle <br />access, a separate zone by floor shall be provided for all of the following <br />types of alarm - initiating devices where provided• <br />1 . Smoke detectors. <br />2. Sprinkler waterflow devices. <br />3. Manual fire alarm boxes <br />4. Other approved types of automatic detection devices or <br />suppression systems. <br />SECTION 15: That section 8 -106 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows (new language underlined, deleted language in strikeout for tracking <br />purposes only): <br />Sec. 8 -106. °��.T�� Sprinkler buildings (Section 910.3.2.2). <br />Section 910.3.2.2 is amended to read as a follows: <br />fFl 910 3 2 2 Sprinkler buildings Where installed in buildings provided with <br />an approved automatic sprinkler system, smoke and heat vents shall be <br />designed to operate automatically by actuation of a heat - responsive <br />device rated at least 100° F above the operating temperature of the <br />sprinkler, unless otherwise approved. <br />SECTION 16: That section 8 -109 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows (new language underlined, deleted language in strikeout for tracking <br />purposes only): <br />Sec. 8 -109. °es�T�� (Section 1505.5). <br />Section 1505.5 of the building code is deleted. <br />SECTION 17: That section 8 -110 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows (new language underlined, deleted language in strikeout for tracking <br />purposes only): <br />Sec. 8 -11 O. °es�Te�� (Section 1505.7). <br />Ordinance No. NS -XXXX <br />7C A _� � Page 9 of 50 <br />