HomeMy WebLinkAboutNS-1163ORDINANCE NS - 1163
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF
SANTA ANA AMENDING AND ADDING TO CHAPTER 8 OF THE
SANTA ANA MUNICIPAL CODE FOR THE PURPOSE OF ADOPTING
AN AMENDMENT TO THE 1970 EDITION OF THE UNIFORM
BUILDING CODE CONCERNING LIFE-SAFETY PROVISIONS FOR
HIGH RISE RESIDENTIAL AND OFFICE BUILDINGS
THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES ORDAIN
AS FOLLOWS:
Section 1: The Santa Ana Municipal Code is hereby
amended by adding a section to be numbered Section 8-158,
which said section reads as follows:
Section 8-158.
Special Life-Safety Provisions
for High Rise Residential and
Office Buildings.
Chapter 17 of the Building Code is amended by adding
a section to be numbered Section 1715 to read as follows:
Section 1715.
Special Provisions For Group F,
Division 2 Office Buildings and
Group H Occupancies.
(a.) Scope. The requirements herein apply to build-
ings housing Group F, Division 2 Occupancies used primarily
as offices and to Group H. Occupancies.
Such buildings having floors used for human occupancy
located more than 75 feet above grade shall conform to the
requirements of this Section in addition to other applicable
requirements of this Code.
(b.) Compartmentation. Compartmentation shall be
provided in every building to provide areas of refuge for
the building occupants. This may be provided by;
1. Horizontal exits dividing a story into two or more areas
of approximately the same size not exceeding 30,000 square
feet.
2. Subdividing the building into five story compartments
by interrupting the stairshaft with smoke barriers every
fifth floor or through the use of smokeproof enclosures for
all stairways or any other method which will protect against
the movement of smoke from one compartment to another.
Openings in exterior walls, located vertically above
one another, shall be protected by approved flame barriers
extending 30 inches beyond the exterior wall in the plane
of the floor or by vertical panels not less than 3 feet
in height.
-1-
ORDINANCE NS - 1163
Horizontal exit walls used for compartmenting a
building shall not have openings therein which would per-
mit transfer of smoke from one compartment to the other
except for required exits. For sprinkler alternate see
Subsection (m).
(c) Fire Alarm. A manual fire alarm box shall be
located adjacent to exit doors into stairway shafts and
in every elevator lobby. The box shall be connected to
the Central Control Station and to the voice communica-
tion system as required by Subsections (f) and (g). The
system shall be designed in accordance with U.B.C. Standard
No. 18-1.
(d) Fire Detectors. An approved system which will
provide for automatic detection of products of combustion
other than heat shall be installed in every mechanical
equipment room and in the return air portion of every air
conditLoning and mechanical ventilation system that serves
floors other than the floor on which the equipment is lo-
cated. The detectors shall be set to operate within the
limitations of U.B.C. Standard No. 43-6 and shall be located
at each opening into the vertical shaft.
(e) Voice Alarm System. Both the detection system
and the fire alarm system shall activate a voice alarm
system capable of being operated from the Central Control
Station on both a general as well as a selective basis
dependent upon the compartmentation involved. The alarm
shall be designed to be heard by all occupants within the
building or designated portions thereof as specified for
the voice communication system. The elevator lobby detec-
tor required by Chapter 51 shall be connected to the system.
(f) Voice Communication System. There shall be two
separate approved continuously electrically supervised
voice communication systems; one for Fire Department
communication system and the other a public voice communi-
cation (address) system between the central control station
and the following areas:
1. Elevators, elevator lobbies, corridors and stairways.
2. Every office area exceeding 1,000 square feet in area.
3. Each dwelling unit and hotel guest room.
When approved, the fire department system may be
combined with the public voice communication system and
voice alarm system.
(g) Central Control Station. A central control
station for Fire Department operations shall be provided
in a location approved by the Fire Department. It shall
contain the voice communication systems panel; fire detec-
tion and alarm system panels; status indicators and controls
for elevators; air handling systems; controls for unlocking
stairway doors; a public telephone; sprinkler valve and
water flow detectors; and standby power controls.
-2-
ORDINANCE NS - 1163
(h) Smoke Control. Natural or mechanical ventilation
for the removal of the products of combustion shall be
provided in every story and shall consist of one or more of
the following:
1. Panels or windows in the exterior wall which can be
opened from an approved location other than the fire floor.
Such venting facilities shall be provided at the rate of
at least 20 square feet per 50 lineal feet of exterior wall
in each story, and distributed around the perimeter at not
more than 50-foot intervals. Such panels shall be clearly
identified as required by the Fire Department.
2. Approved tempered glass may be used in lieu of openable
panels.
3. When fire sprinklers are installed in compliance with
Subsection (m), the mechanical air handling equipment may
be designed to assist smoke removal. Under fire conditions,
the return and exhaust air shall be taken directly to the
outside without recirculation to other sections of the
building.
4. A shaft through which smoke and heat can be mechanically
vented to the outdoors. The size of the shaft shall be uni-
form throughout and of such dimensions as to provide not
less than 60 air changes per hour in the largest compartment
served anywhere in the building. Openings into the shaft
shall be protected with an automatic single piece shutter
located as high in the room as possible and designed to
vent the entire compartment.
5. Any other design which will produce equivalent results.
(i) Elevators. There shall be provided at least one
elevator in each bank available for Fire Department access
to any floor. The elevator shall open into a lobby, which
may serve other elevators, and shall be separated from the
remainder of the building by construction as required for
corridors. The elevator may be located within a smokeproof
enclosure. See Chapter 51 for additional requirements.
(j) Standby Power and Light. A permanently installed
standby power generation system conforming to U.B.C. Stan-
dard No. 18-1 shall be provided. The system shall be
equipped with suitable means for automatically starting
the generator set upon failure of the normal electrical
service and for automatic transfer and operation of all the
required electrical functions at full power within 60
seconds of such normal service failure. System supervision
with manual start and transfer features, shall be provided
at the Central Control Station.
An on-premise fuel supply sufficient for not less than
two hours full demand operation of the system shall be pro-
vided. All power, lighting, signal, and communication
facilities provided under the requirements of this Section
shall be transferable to the standby power system.
-3-
ORDINANCE NS - 1163
The power requirement shall be deteuamined so as to
provide service to, but not limited to the following:
1. Fire alarm system.
2. Exit and other emergency lighting.
3. Fire protection equipment.
4. Mechanical ventilation required by this Section.
5. Fire Department elevator.
6. Voice communication system.
(k) Seismic Considerations. In Seismic Zones 2 and 3
the anchorage of the following mechanical and electrical
equipment required by the Section shall be designed in
accordance with Section 2314 for a lateral force based on
a "Cp" value of 0.5 unless data substantiating a lesser
value is furnished:
1. Elevator drive and suspension systems.
2. Standby power and lighting facilities.
3. Fire pumps and other fire protection equipment.
(1) Exits. Ail Stairway doors which are to be locked
from the stairway side shall have the capability of being
unlocked upon a signal from the Central Control Station.
Emergency telephones available to the public shall be
provided at not less than'every fifth floor in each required
stairway.
(m) Fire Sprinkler Alternative. Sprinkler protec-
tion conforming to the following may be provided as an
alternate to compartmentation:
1. The sprinkler system is hydraulically designed using the
parameters set forth in U.B.C. Standard No. 38-1 and the
following:
(i) Shutoff valves and waterflow devices shall be
provided on each floor. In addition to actuating a local
alarm on the floor upon which the water flow is detected,
such valves shall be supervised by a continuously manned con-
trol station or by a central station.
pipe
with
loop
(ii) The sprinkler system shall be looped between stand-
risers at the bottom, top and mid-height of all buildings
a maximum of 20 stories served by any loop. At each
level there shall be check valves.
(iii) Piping may be copper or steel with no minimum
size of pipe required. Solder used in connections shall
contain not less than 95 percent tin and 5 percent antimony.
(iv) Pitching of lines is not required.
(v) A minimum of two fire pumps independently driven
shall be provided and sized for the sprinkler demand and for
a minimum 500 gallons per minute Fire Department standpipe
operations.
(vi) An on -site supply of water equal to a 20-minute
demand or 15,000 gallons on a combined sprinkler and stand-
pipe, whichever is the smaller, shall be provided. This
supply shall be available automatically if the principal
supply fails.
-4-
ORDINANCE NS - 1163
(vii) Operation of the sprinkler system shall activate
the voice communication system.
2. When the automatic sprinkler system described above is
installed, the following reductions from the requirements
of this Code are permitted:
(i) The fire-resistive time periods set forth in Table
No. 17-A may be reduced by one hour for interior bearing
walls, exterior bearing and non-bearing walls, roofs and the
beams supporting roofs, provided they do not frame into
columns. All office building partitions required to be of
one-hour fire-resistive construction by Table No. 17-A and
Section 3304 (g) may be of noncombustible construction with-
out a fire-resistive time period. Openings in corridor walls
shall be protected by tight-fitting, self-closing doors that
need not have a fire-resistive time period. In Group H
Occupancies, corridor and dwelling unit or guest room separa-
tion may be reduced to one-half hour.
(ii)
omitted.
The 1 1/2 inch hose lines and nozzles may be
(iii) Travel distance to a horizontal exit or to an
enclosed stairway may be 300 feet.
(iv) Smokeproof enclosures may be eliminated if each
required stairway is pressurized as provided in Section
3309 (h) to .15 inch of water column.
(v) Spandrel protection required by Subsection (b)
may be omitted.
SECTION 2: If any section, subsection, sentence, clause,
phrase or portion of this ordinance is for any reason held to
be invalid or unconstitutional by the decision of any court of
competent jurisdiction, such decision shall not affect the
validity of the remaining portions of this ordinance. The City
Council of the City of Santa Ana hereby declares that it would
have adopted this ordinance and each section, subsection, sen-
tence, clause, phrase or portion thereof irrespective of the
fact that any one or more sections, subsections, clauses,
phrases or portions be declared invalid or unconstitutional.
SECTION 3: Neither the adoption of this ordinance
nor the repeal hereby of any ordinance shall in any manner
affect the prosecution for violation of ordinances, which
violations were committed prior to the effective date hereof,
nor be construed as affecting any of the provisions of such
ordinances relating to the collection of any such license
or penalty or the penal provisions applicable to any viola-
tion thereof, nor to affect the validity of any bond or case
deposit in lieu thereof, required to be posted, filed or
deposited pursuant to any ordinance, and all rights and obli-
gations thereunder appertaining shall continue in full force
and effect.
SECTION 4: The Clerk of the Council shall certify to the
passage of this ordinance and cause the same to be published
in some daily newspaper printed and published in the City of
Santa Ana.
-5-
ORDINANCE NS 1163
PASSED AND ADOPTED by the City Council of the City of
Santa Ana at its regular meeting held on the ~th day of
, 1973.
ATTEST:
CLERK OF THE COUNCIL
STATE OF CALIFORNIA )
COUNTY OF ORANGE ) ss
CITY OF SANTA ANA )
I, FLORENCE I. MALONE, do hereby certify that I a~
the Clerk of the Council of the City of Santa Ana; that
the foregoing Ordinance was introduced to said Council at
its regular meeting held on the 21st day of
May , 1973 and was again considered by
said Council at its meeting held on the 4th day of
June , 1973, and was at said meeting passed and
adopted by the following vote, to wit:
AYES, COUNCILMEN:
NOES, COUNCILMEN:
Griset, Yamamoto, Markel, Garthe, Patterson,
Ward
None
ABSENT, COUNCILMEN: Evans
CLERK OF THE COUNCIL