HomeMy WebLinkAboutNS-1416REL: nr
ORDINANCE NO. NS-1416
AN ORDINANCE OF THE CITY OF SANTA ANA
AMENDING SECTION 8-1 OF THE SANTA ANA
MUNICIPAL CODEr PERTAINING TO THE APPLI-
CATION AND SCOPE OF CHAPTER 8 THEREOF,
AND AMENDING ARTICLE V OF SAID CHAPTER 8
TO ADOPT THE NATIONAL ELECTRICAL CODE,
1975 EDITION, WITH AMENDMENTS AND ADDI-
TIONAL REQUIREMENTS.
THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES
ORDAIN AS FOLLOWS:
SECTION 1: Section 8-1 of the Santa Ana Municipal
Code is hereby amended to read as follows:
Sec. 8-1. Application and scope.
If any provision of this chapter conflicts with the
regulations of the Commission of Housing and Community Develop-
ment adopted pursuant to the State Housing Law (Health and
Safety Code Sections 17910 et seq.), such provision shall apply
to an activity subject to such regulations only if either the
provision was in effect prior to November 23, 1970, or the pro-
vision was enacted pursuant to Sections 17958.5 and 17958.7 of
the State Housing Law.
SECTION 2: That Section 8-667 of the Santa Ana Muni-
cipal Code is hereby amended to read as follows:
Sec. 8-667. Adoption by reference.
There is adopted by the city that certain code known
as the National Electrical Code, 1975 Edition, and the whole
thereof save and except such portions as are deleted by the
amendments set forth in this Article, of which said code not
less than three (3) copies have been and are on file in the
office of the clerk of the council of the city. The said code
is adopted and incorporated as fully as if set forth at length
herein, as provided for in Section 419 of the Charter of the
City, and, subject to all amendments set forth in this article,
shall be in effect within the City of Santa Ana from the effec-
tive date of this ordinance. Any provision of this article
amending the "Electrical Code" or "National Electrical Code"
shall be construed as amending the said adopted code, 1975
Edition, including such provisions enacted prior to the enact-
ment of this ordinance and not thereafter repealed. The said
adopted code, 1975 Edition, as thus amended, together with all
other provisions of this article, shall be known as the Elec-
trical Code of the City of Santa Ana.
SECTION 3: That the following sections of the Santa
Ana Municipal Code are hereby repealed: 8-699, 8-700, 8-710,
8-719, 8-729, 8-741, 8-756, 8-785, 8-797, 8-810, 8-826, 8-837,
8-857, 8-879, 8-896, 8-916, 8-928, 8-940, 8-942, 8-953, 8-969,
8-979, 8-1000, 8-1010, 8-1023, 8-1034, 8-1050, 8-1070, and
8-1090.
ORDINANCE NO. NS- 1416
PAGE TWO
SECTION 4: That the Santa Ana Municipal Code is
hereby amended by adding a Division to be numbered 2 to Article
V of Chapter 8, said Division to consist of sections numbered
8-700 through 8-799 inclusive and to read as follows:
DIVISION 2. ADMINISTRATION AND ADDITIONAL
REQUIREMENTS
Sec. 8-700. Enforcement.
The director of building safety of the city is vested
with the authority to enforce all of the provisions of this code
and shall have the right to enter upon any premises at all
reasonable hours for the purpose of inspecting the installation
and working of all apparatus coming within the terms of this
article and no person shall interfere with the director of build-
ing safety in making the inspections or refuse to permit the
director of building safety or his deputies to enter the premises
for such purposes.
Sec. 8-705. Penalties.
(a) This code shall not be construed to relieve from
or lessen the responsibility of any party owning, operating, con-
trolling or installing any electric wiring, electric devices or
electric materials for damages to persons or property caused by
any defect therein, nor shall the jurisdiction be held as assum-
ing any such liability by reason of the inspection authorized
herein or certificate of inspection issued as herein provided.
(b) The director of building safety is authorized to
determine the intent and meaning of any provisions of this code.
(c) Any person violating any of the provisions of
this code shall be guilty of a misdemeanor.
(d) Every person violating any of the provisions of
this code shall be deemed guilty of a separate offense for each
day or portion thereof during which such violation continues.
(e) It is unlawful for any person, either as owner,
architect, contractor, artisan, or otherwise, to do or knowingly
to cause or permit to be done any electrical wiring as defined
in this code in such manner that the same shall not conform to
all of the provisions of this code.
Sec. 8-711. Permits.
No electrical equipment shall be installed within or
on any building, structure or premises, publicly or privately
owned, nor shall any alteration or addition be made in any such
existing equipment without first securing a permit therefor
from the director of building safety, except for minor repair
work, such as the replacement of lamps or the repair and con-
nection of portable electrical equipment to suitable permanently
installed receptacles.
ORDINANCE NO. NS-1416
PAGE THREE
Sec. 8-712. Same - issuance.
Permits may be issued only to a person, firm or cor-
poration licensed by the state in the classification authorized
to perfor~ the work and subject to the conditions and limitations
of such classification, or to a person, firm, or corporation
qualifying under section 8-714, or to an owner qualifying under
section 8-715.
Sec. 8-713. Same - applications.
Applications for electrical permits, describing the
work to be done, shall be made in writing to the director of
building safety. The application shall be accompanied by such
plans, specifications and schedules as may be necessary to deter-
mine whether the installations as described will be in conformity
with the requirements of the sections in this code pertaining to
electricity. If it shall be found that the installation as des-
cribed will conform to all legal requirements, and if the appli-
cant has complied with the provisions of the sections in this
code pertaining to electricity, a permit for such installation
may be issued upon receipt of fees therefor, as prescribed in
section 8-722. No deviation may be made from the installation
described in the permit without the written approval of the
director of building safety.
Sec. 8-714. Same - annual permits.
An annual permit may be issued to any person, firm,
or corporation regularly employing a maintenance electrician
approved by the director of building safety. The maintenance
electrician may install, alter, maintain, or repair electrical
wiring in or on buildings or premises owned or occupied by his
employer and shall keep a detailed record of all such work.
Within fifteen (15) days following the end of each calendar
month, the maintenance electrician shall file an application
accompanied by regular fees and obtain an electrical permit
for all electrical work accomplished during the preceding month.
Sec. 8-715. Same - license requirement.
As a condition to the issuance of an electrical per-
mit, the applicant must s~gn a statement that he is licensed
under the provisions of the California Business and Professions
Code, Division 3, Chapter 9 (Contractor's License Law) giving
the number of the valid license, or, if the applicant is exempt
fr~m the provisions of this chapter, the basis for the alleged
exemption.
Sec. 8-716. Same - commencement of work.
No electrical work for which a permit is required
shall be commenced in any building or premises until a permit
to do such work shall have been first obtained.
Sec. 8-717. Same - penalty.
Failure to obtain a permit and pay fees therefor
before commencing work shall be deemed evidence of violation
of the provisions of this code. Double the amount of permit
fee shall be assessed for work commenced before a permit is
issued.
ORDINANCE NO. NS-1416
PAGE FOUR
Sec. 8-718. Sa~e - non-transferability.
No permit shall be transferable. A permit granted
to any one person, firm or corporation shall not authorize
any other person, firm or corporation, except an employee of
the permittee, to do any electric wiring.
Sec. 8-719. Same - temporary working permits.
When, in the opinion of the director of building safety,
special conditions warrant, a temporary working permit may be
issued to allow the permittee to commence the installation of
electrical wiring prior to obtaining a regular electrical permit.
However, the temporary working permit shall be replaced by a
regular electrical permit before the complete rough inspection
can be made.
Sec. 8-720. Same - expiration.
Every permit shall expire and become null and void
for any one or more of the following reasons:
Whenever the electric wiring authorized by a
permit is not commenced within sixty (60) days
from the date of issuance of such permit.
e
Whenever the electric wiring authorized by a
permit has been suspended, abandoned or discon-
tinued for a continuous period of one hundred
twenty (120) days.
Whenever the electric wiring done during any
continuous period of ninety (90) days amounts
to less than ten (10) per cent of the total
of the electric wiring authorized by such per-
mit.
Before rec~mmencing, proceeding with, or doing any electric wir-
ing authorized by but not done before expiration of any such
permit, a new permit shall be obtained therefor, and the fee for
such permit shall be the fee required for a new permit.
Sec. 8-721. Same - revocations and suspensions.
The director of building safety may suspend or revoke
any electrical permit for any of the following reasons:
If any reason is found to exist which would have
been cause for denial of such permit.
Any material misrepresentation or falsity in the
application upon which said permit was issued.
e
For failure to comply with the provisions of the
sections in this code pertaining to electricity;
after due notice of corrections and the time limit
therefor has expired; or for failure to comply
with other codes of this jurisdiction that may
be related to or appertain to the sections in
this code pertaining to electricity.
Sec. 8-722. Permit fees.
Fees for the processing of permit applications, plan
checking, and other administrative services shall be established
by resolution of the city council. Such fees must be paid to
the Director of Building Safety for each electrical installation
for which a permit is required by this code. No permit shall be
issued unless all fees are paid in full.
ORDINANCE NO. NS-1416
PAGE FIVE
Sec. 8-728. Hidden installations.
When any part of a wiring installation is to be
hidden from view, the person, firm or corporation installing
the wiring shall notify the director of building safety and
such parts of the wiring installation shall not be concealed
until they have been inspected and approved by the director
of building safety.
Sec. 8-729. Inspections and corrections.
Upon completion of the work which has been autho-
rized by issuance of any permit, except an annual permit, it
shall be the duty of the person, firm, or corporation installing
the same to notify the director of building safety who shall
inspect the installation as soon thereafter as practicable.
If, upon inspection, the installation is not found to be in con-
formity with the provisions of this code, the director of build-
ing safety shall notify the person, firm, or corporation making
the installation, stating the defects which have been found to
exist. All defects shall be corrected within ten (10) days
after inspection and notification, or within other reasonable
time as permitted by the director of building safety. No
electrical installation shall be energized until inspected and
approved by the director of building safety.
Sec. 8-730. Temporary connections.
When authorizing the connection and use of temporary
or incomplete work, such authorization shall expire at a time
to be stated by the director of building safety.
Sec. 8-740. Standards for the installation of
electrical equipment.
Ail electrical installations;industrial, commercial,
and residential, within the governmental jurisdiction covered
by this chapter shall be in conformity with the provisions of
this article, all applicable State laws, and National Fire Pro-
tective Association standards for safety to life and property.
Sec. 8-741. Approval of equipment.
Ail appliances and equipment shall be listed and labeled
by a nationally recognized testing laboratory equal to but not
limited to Underwriter's Laboratories, Inc., and approved by the
director of building safety.
Sec. 8-742. Used materials.
Previously used materials shall not be re-used without
the written approval obtained in advance from the director of
building safety.
Sec. 8-743. Nameplates.
The maker's nameplate, trademark, or other identifi-
cation symbol shall be placed on the outside where it is visible
at time of inspection on all electrical materials, devices,
appliances, fittings and equipment used or installed under the
provisior~of this code.
ORDINANCE NO. NS-1416
PAGE SIX
Sec. 8-747. Underground installations
Whenever any property is developed with new or
relocated buildings or structures; or whenever floor area
in excess of fifty percent (50%) of the existing floor
area is added to an existing building; or whenever a resi-
dential building or use is converted to any purpose or use
other than that which existed at the time of the conversion,
all electrical, telephone, community antenna television and
similar service wires or cables which provide direct service
to the property being developed, added to, or converted,
shall, within the exterior boundary lines of such property,
be installed underground. Conduits required for telephone
or community antenna television shall be installed to
utility specifications by the electrical permit holder prior
to inspection of electrical conduit. Lots of record as of
November 19, 1969, which are developed for R-1 use, are
exempted from the requirements of this section.
Sec. 8-765. Same change of occupancy
classification.
When any building or structure, or portion thereof
is placed in a different occupancy classification, those
portions directly affected by such occupancy change shall
be wired in compliance with the provisions of this article
for the new occupancy.
Sec. 8-769. Relocated buildings
Relocated buildings shall conform to the minimum
standards as required in this article for new buildings.
SECTION 5: That the Santa Ana Municipal Code is
hereby amended by adding a Division to be numbered 3 to
Article V of Chapter 8, said Division to consist of sections
numbered 8-800 through 8-1155 inclusive and to read as
follows:
DIVISION 3. AMENDMENTS
Sec. 8-803. Purpose (Section 90-1(a))
Section 90-1(a) of the National Electrical Code is
amended by adding a second sentence to read as follows:
To accomplish this purpose, the requirements
set forth in this Electrical Code shall be
the minimum standard for electrical install-
ations.
Sec. 8-805. Scope (Section 90-2(a))
Sec. 90-2(a) of the National Electrical Code is
amended to read as follows:
(a)
Covered. This Code shall cover all wiring
and equipment installed, used, or maintained
except such electrical wiring and equipment
expressly exempted from the provisions of this
code.
ORDINANCE NO. NS-1416
PAGE SEVEN
Sec. 8-815. Conductors (Section 110-5)
Section 110-5 of the National Electrical Code is
amended by adding a second sentence to read as follows:
Ail sections of this National Electrical Code
allowing the use of aluminum conductors are sub-
ject to the limitation that no aluminum conduc-
tor smaller than #6 AWG shall be used.
Sec. 8-821. Scope of Article 210 (Section 210-1).
Section 210-1 of the National Electrical Code is
amended by adding paragraphs designated (a) and (b) to read as
follows:
(a)
Accessory uses or other buildings, signs, etc.
separately located on the same lot or premises
shall have connecting conductors run under-
ground. (Agricultural areas excepted.)
(b)
Where space circuit protective devices are
provided or space for future circuit protec-
tive devices is provided on the buss in any
flush or semi-flush mounted panel, then
raceways of sufficient capacity to permit
utilization of such space or spaces shall be
provided to an approved accessible location.
Such accessible location is normally defined
as follows: Where sufficient attic space is
available or underfloor space is available,
a raceway shall terminate conveniently for
future use in each such space. Where this
condition does not exist or other factors
govern, then such terminations shall be
approved by the enforcing authority.
Sec. 8-823. Conductors - Minimum Ampacity and
Size (Section 210-19(c))
The first paragraph of section 210-19(c) of the
National Electrical Code is amended to read as follows:
(c)
Other Loads. Branch-circuit conductors supply-
ing loads other than cooking appliances as
covered in (b) above and as listed in Section
210.2 shall have an ampacity sufficient for
the loads served and shall not be smaller than
No. 12. For the supply of current to general
appliance and convenience receptacle circuits,
no conductor smaller than No. 12 AWG shall be
installed.
Sec. 8-828. Receptacle Outlets Required (Section
210-25(b)).
Section 210-25(b) of the National Electrical Code
amended by amending the sixth paragraph thereof to read as
follows:
is
At least one receptacle outlet shall be installed
in each basement, garage, and carport. Garages
or carports accessory to dwelling units shall be
wired with a minimum of one receptacle per each
two auto stalls or fractions thereof.
Exception: In hotel, motel, and multiple
occupancies, garage and carport receptacles may
be omitted.
ORDINANCE NO. NS-1416
PAGE EIGHT
Sec. 8-829. Lighting Outlets Required (Section
210-26(a)).
The first sentence of Section 210-26(a) of the
National Electrical Code is amended to read as follows:
At least one wall switch controlled lighting out-
let shall be installed in every habitable room;
in hallways, stairways, garages, and carports;
and at outdoor entrances.
Sec. 8-839. Feeders (Article 215).
Article 215 of the National Electrical Code is
a~ended by adding a section designated 215-10 thereto to read
as follows:
215-10. Raceways. Ail feeder conductors shall
be installed in an approved raceway.
Sec. 8-843. Branch circuits required (Section
220-3).
Section 220-3 of the National Electrical Code is
~mended by adding three sentences to the introductory paragraph
thereof to read as follows:
No convenience receptacle or appliance receptacle
shall be installed or operated on a general light-
ing branch circuit at any time in any occupancy.
A one-half hot and one-half switched receptacle
may be installed on a lighting branch circuit
when used as the lighting outlet required for
habitable rooms permitted in 210.26(a) Exception
NO. 1. A maximum of 12 convenience receptacle
outlets or 12 lighting outlets to any one circuit.
Sec. 8-854. Wiring Methods for 600 Volts or Less
(Section 230-43).
Section 230-43 of the National Electrical Code is
hereby amended to read as follows:
230-43. Wiring Methods for 600 Volts or Less.
Service entrance conductors extending along the
exterior or entering buildings or other structures
shall be enclosed in rigid metal conduit to the
first over current device, or, for circuits not
exceeding 600 volts, in wire ways, auxiliary gut-
ters, or as busways.
Sec. 8-856. Maximum Number of Disconnects (Sec~
tion 230-71).
Section 230-71 of the National Electrical Code is
a~ended to read as follows:
230-71. Disconnection from service conductors.
A single fusible switch or automatic circuit
breaker shall be provided to disconnect all un-
grounded conductors supplying each separately
metered occupancy.
ORDINANCE NO. NS-1416
PAGE NINE
Sec. 8-863. Made Electrodes (Section 250-83).
Section 250-83 of the National Electrical Code is
amended to read as follows:
250-83. Made Electrodes. Where electrodes des-
cribed in Section 250.81 and 250.82 are not avail-
able, the grounding electrode shall consist of not
less than 20 feet of bare copper conductor not
smaller than No. 4; or not less than 20 feet of No.
4 steel reinforcing bar; or not less than 20 feet
of 3/4 inch galvanized steel conduit; or an
approved equal installed as follows:
The electrode shall be located in the bottom
of the foundation footing with minimum con-
crete encasement of 3 inches. One end of the
electrode shall extend out of the foundation
adjacent to the equipment to be grounded to
permit the grounding conductor to be secured
by an approved method.
EXCEPTION:
Where the above method is not
practical, the following electrodes
may be used upon approval of the
enforcing authority;
(1)
Plate Electrodes. Each plate electrode
shall present not less than 2 square feet
of exterior soil. Electrodes of iron or
steel plates shall be at least 1/4 inch
in thickness. Electrodes of nonferrous
metal shall be at least 0.06 inch in
thickness.
(2)
Pipe Electrodes. Electrodes of pipe or
conduit shall be not smaller than of the
3/4 inch trade size and where of iron or
steel, shall have the outer surface gal-
vinized or otherwise metal-coated for
corrosion protection. Minimum of 8 feet
to be driven in the ground.
(3)
Rod Electrodes. Electrodes of rods of
steel or iron shall be at least 5/8 inch
in diameter. Approved rods of non-ferrous
materials or their approved equivalent used
for electrodes shall be not less than 1/2
inch in diameter. Minimum of 8 feet to be
driven in the ground.
Sec. 8-867. Connection to Electrodes (Section 250-115).
Section 250-115 of the National Electrical Code is
amended by adding thereto a sentence to be designated (e) to
read as follows:
(e) The service ground clamp shall be readily
accessible.
ORDINANCE NO. NS-1416
PAGE TEN
Sec. 8-913. Mechanical and Electrical Continuity-
Conductors (Section 300-13(b)).
Section 300-13(b) of the National Electrical Code is
a~ended to read as follows:
(b) In all circuits the continuity of conductors
shall not be dependent upon device connections, such
as lampholders, receptacles, etc., where the removal
of such devices would interrupt the continuity.
Sec. 8-915. Boxes or Fittings - Where required
(Section 300-15(b)).
Section 300-15(b) of the National Electrical Code is
amended by deleting therefrom Exceptions numbers 1 and 5.
Sec. 8-933. Metal-Clad Cable (Article 334).
Chapter 3 of the National Electrical Code is amended
by deleting therefrom Article 334 and all sections therein in-
cluded, to wit: Sections 334-1 through 334-13 inclusive.
Sec. 8-941. Uses Permitted or Not Permitted (Section
336-3).
Section 336-3 of the National Electrical Code is
amended to read as follows:
336-3. Uses Permitted or Not Permitted. Non-
metallic sheathed cable shall not be used for ex-
posed wiring and shall only be used for concealed
wiring in one and two family dwellings or multi-
family dwellings (apartment houses) not exceeding
three floors above grade.
(a)
Type NM. This type of non-metallic sheathed
cable may be installed for concealed work in
normally dry locations. It may be installed
or fished in air voids in masonry block or
tile walls where such walls are not exposed or
subject to excessive moisture or dampness.
Type NM cable shall not be installed where
exposed to corrosive fumes or vapors; nor shall
it be embedded in masonry or concrete and covered
with plaster or similar finish.
(b)
Moisture and Corrosion-Resistant Type NMC.
This type of non-metallic sheathed cable may be
installed for concealed work in dry, moist, damp
or corrosive locations, and in outside and in-
side walls of masonry block or tile. Where em-
bedded in plaster or run in shallow chase in
masonry walls and covered with plaster within
2 inches of the finished surface, it shall be
protected against damage from nails by a cover
of corrosion-resistant coated steel at least
1/16 inch in thickness and 3/4 inch wide in the
chase or under the final surface finish.
ORDINANCE NO. NS-1416
PAGE ELEVEN
Sec. 8-943. Exposed Work - General (Section 336-6).
Article 336 of the National Electrical Code is amended
by deleting therefrom Section 336-6.
Sec. 8-945. Devices of Insulating Material (Section
336-11).
Article 336 of the National Electrical Code is amended
by deleting therefrom Section 336-11.
Sec. 8-961. Use of Electrical Metal Tubing (Section
348-1).
Section 348-1 of the National Electrical Code is
amended to read as follows:
348-1. Use. Electrical metallic tubing may be used
for both exposed and concealed work. Electrical metal-
lic tubing protected from corrosion solely by enamel
shall not be used. Electrical metallic tubing shall
not be used (1) where during installation or afterwards,
it will be subject to severe physical damage; (2) for
installation underground or in concrete. Where prac-
ticable the use of dissimilar metals throughout the
system shall be avoided to eliminate the possibility
of galvanic action. (3) Electrical metallic tubing
shall not be used where exposed directly to the wea-
ther or excessive moisture.
Sec. 8-972. Use of Flexible Metal Conduit (Section
350-2).
Section 350-2 of the National Electrical Code is
amended to read as follows:
350-2. Use. Flexible metal conduit shall not be used
(1) in wet locations unless conductors are of the
lead-covered type or of other type specifically approved
for the conditions; (2) in hoistways, other than as
provided in Section 620-21; (3) in storage battery rooms;
(4) in any hazardous location other than permitted in
Sections 501-4(b), 502-4 and 503-3; nor (5) where rub-
ber-covered conductors are exposed to oil, gasoline,
or other materials having a deteriorating effect on
rubber; (6) for installation underground, exposed to
the water, embedded in masonry, concrete, adobe, plas-
ter or similar finish; (7) where exposed to physical
damage.
Sec. 8-1018. Fixtures in Clothes Closets (Section
410-8).
Section 410-8 of the National Electrical Code is
amended by adding a sentence designated (c) to read as follows:
(c) All lighting outlets shall be operated by a wall
or door switch (no pull chain lighting fixtures per-
mitted).
ORDINANCE NO. NS- 1416
PAGE TWELVE
Sec. 8-1025. Branch-Circuit Sizing (Section 422-5).
Section 422-5 of the National Electrical Code is
a~ended by adding a paragraph designated (c) to read as follows:
(c) In every dwelling unit fixed appliances, such as
food grinders, dishwashers, washing machines, dryers,
laundry tray locations, built-in heaters, or any
other fixed appliances with 1/4 H.P. motor or larger
shall be on a separate branch circuit supplied by a
minimum No. 12 AWG Wire. Each dwelling unit shall
have installed therein an individual food waste grinder
branch circuit. Said circuit shall be supplied with a
minimum No. 12 AWG wire and a 15 ampere indicating type
switch. Said switch shall be located in the wall
adjacent to the sink. Food waste grinder shall be
wired with a minimum of No. 16 AWG 3-wire S.P.To -3
thermo-plastic hard finish cord or equal and an approved
grounding type, cord grip cap must be used.
Sec. 8-1080. Scope of Article 600 (Section 600-1).
Section 600-1 of the National Electrical Code is
amended by adding a sentence thereto to read as follows:
A sign circuit shall be provided and installed to
an accessible location at the front of all commercial
and store buildings.
SECTION 6: If any section, subsection, sentence,
clause, phrase or portion of this ordinance is for any reason held
to be invalid or unconstitutional by the decision of any court of
competent jurisdiction, such decision shall not affect the validity
of the remaining portions of this ordinance. The City Council of
the City of Santa hereby declares that it would have adopted
this ordinance and each section, subsection, sentence, clause,
phrase or portion thereof irrespective of the fact that any one or
more sections, subsections, sentences, clauses, phrases or portions
be declared invalid or unconstitutional.
SECTION 7: Neither the adoption of this ordinance nor the
repeal hereby of any ordinance shall in any manner affect the pro-
secution for violation of ordinances, which violations were com-
mitted prior to the effective date hereof, nor be construed as affect-
ing any of the provisions of such ordinance relating to the collection
of any such license or penalty or the penal provisions applicable
to any violation thereof, nor to affect the validity of any bond or
cash deposit in lieu thereof, required to be posted, filed or de-
posited pursuant to any ordinance and all rights and obligations
thereunder appertaining shall continue in full force and effect.
PASSED AND ADOPTED by the City Council of the City of
Santa Ana at its regular meeting held on the 27th
day of June , 197~.
ATTEST:
FLORENCEI. MALONE
MAYOR
ORDINANCE NO.
PAGE THIRTEEN
NS-1416
STATE OF CALIFORNIA )
COUNTY OF ORANGE ) ss
CITY OF SANTA ANA )
I, FLORENCE I. MALONE, do hereby certify that I am the
Clerk of the Council of the City of Santa Ana; that the fore-
going Ordinance was introduced to said Council at its
Regular meeting held on the 19th day of 3une ,
197 8, and was again considered by sa--~Council at its
Regular meeting held on the 27th : day of June ,
1978, and was at said meeting passed and adopted by the following
vote, to wit:
AYES, COUNCILMEN: Brandt, Garthe, 0rtiz, Yamamoto,
Ward
NOES, COUNCILMEN:Bricken
ABSENT,
COUNCILMEN: Evans
ELORSNCE I. MALON~
CLERK OF THE COUNCIL x ~ \
APPROVED AS TO FORM:
KEITH L. GOW,
CITY ATTORNEY
STATE OF CALI