HomeMy WebLinkAboutNS-1518CTD/fm
1/10/80
ORDINANCE NO. NS-15t8
AN ORDINANCE OF THE CITY OF SANTA ANA AMENDING THE
SANTA ANA MUNICIPAL CODE BY ADDING ARTICLE XI
CONSISTING OF NEW SECTIONS 8-2000 THROUGH 8-2007,
INCLUSIVE, TO CHAPTER 8, PROVIDING FOR EARTHQUAKE
HAZARD REDUCTION IN EXISTING BUILDINGS.
THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES
ORDAIN AS FOLLOWS:
That the Santa Ana Municipal Code is hereby amended
by adding Article XI consisting of sections 8-2000 through
8-2007, inclusive, to Chapter 8, which said Article shall
read as follows:
ARTICLE XI. EARTHQUAKE HAZARD REDUCTION IN EXISTING BUILDINGS.
Sec. 8-2000. PURPOSE
The purpose of this Article is to promote public
health, safety and welfare by reducing the risk of death or
injury that may result from the effects of earthquakes on
unreinforced masonry buildings. Such buildings have caused
substantial damage and danger when they have collapsed
during past moderate to strong earthquakes.
The provisions of this Article establish minimum
standards for structural seismic resistance primarily to
reduce the risk of death or injury but cannot prevent all
loss of life or injury or prevent earthquake damage to an
existing building even though it complies with these standards.
This Article shall not require existing electrical, plumbing,
mechanical or fire safety systems to be altered unless they
consitute a hazard to life or property.
This Article provides systematic procedures and
standards for identification and classification of unrein-
forced masonry buildings based on their present use. Priorities
and standards are also established under which these buildings
are required to be structurally analyzed. Where the analysis
or testing determines deficiencies, this Article requires
the building to be strengthened to minimum levels required
for compliance or to be demolished.
SEC. 8-2001. SCOPE
The provisions of this Article shall apply to all
existing buildings constructed with unreinforced masonry
walls as defined herein.
EXCEPTION: This Article shall not apply to detached
dwellings or apartment houses containing fewer than 5
dwelling units.
SEC. 8-2002. DEFINITIONS
For the purpose of this Article, the following
terms shall be construed as follows:
A. ESSENTIAL BUILDINGS: Those structures or buildings
which are used for emergency purposes after an earthquake in
order to preserve the peace, health and safety of the general
public. Such facilities shall include the following:
hospitals and other medical facilities having surgery or
emergency treatment areas; fire and police stations; municipal
government disaster operation centers; and public utility
and communication buildings deemed to be vital in emergencies.
ORDINANCE NO. NS-15t8
Page Two
B. HIGH RISK BUILDINGS: Any building, other than an
essential building, having an occupant load of 100 occupants
or more as determined pursuant to Chapter 33 of the Uniform
Building Code and which said building is occupied for its
intended use for more than 20 hours per week.
EXCEPTION: High risk buildings shall not include
buildings having exterior walls braced with masonry cross
walls or wood frame cross walls spaced less than 40 feet
apart in each story.
C. LOW RISK BUILDINGS: Any building, other than an
essential building, having a capacity of less than 20
occupants determined pursuant to Chapter 33 of the Uniform
Building Code.
D. MEDIUM RISK BUILDINGS: Any building having an
occupant load of 20 occupants or more as determined pursuant
to Chapter 33 of the Uniform Building Code that is not
classified as a high risk building or an essential building.
E. UNREINFORCED MASONRY WALL: A masonry wall contain-
ing less than one-half the reinforcing steel required for
reinforced masonry walls in accordance with Chapter 24 of
the Uniform Building Code.
Safety.
DEPARTMENT: Shall mean Department of Building
G. DIRECTOR: Shall mean the Director of Building
Safety or h--~ designated representative.
SEC. 8-2003. RATING CLASSIFICATION
A. CLASSIFICATION: The rating classifications as
exhibited in Table A are hereby established and each building
within the scope of this Article shall be placed in one such
rating classification by the Director.
TABLE A
RATING CLASSIFICATIONS
GENERAL USE OF BUILDING
RATING CLASSIFICATION
Essential Buildings
High Risk Buildings
Medium Risk Buildings
Low Risk Buildings
I
II
III
IV
For the purpose of this Article, portions of
buildings constructed to act independently when resisting
seismic forces may be placed in separate rating classifications.
B. MULTIPLE CLASSIFICATIONS. For the purpose of
determining a Rating Classification, a building with more
than one rating classification shall be classified in the
Rating Classification which is the most restrictive.
C. MULTIPLE OCCUPANCIES. For the purpose of de-
termining rating classifications the total occupant load as
determined pursuant to Chapter 33 of the Uniform Building
Code of all occupancies in the building shall be used.
ORDINANCE NO. NS-I~8~
Page Three
SEC. 8-2004. ADMINISTRATION
A. PRIORITY OF NOTIFICATION. The Director shall
notify owners of buildings within the scope of this Article
in accordance with the rating classifications as set forth
in Table A. In general, buildings having a rating classification
of I shall be notified first; buildings having a rating
classification of II shall be notified second, but not
earlier than six months after the effective date of this
Article; buildings having a rating classification of III
shall be notified third, but not earlier than 18 months
after the effective date of this Article; and buildings
having a rating classification of IV shall be notified last,
but not earlier than five years after the effective date of
this Article. Within each separate Rating Classification,
the notification shall normally be based on the occupant
load of the building, with the buildings housing larger
occupant loads being notified first. Upon receipt of a
written request from the owner, the Director shall serve
notification ordering a building into compliance with this
Article prior to the normal notification date set forth in
this Section.
B. NOTIFICATION. Following the priorities listed in
Subsection 8-2004 (A), the Director shall serve notice
ordering the owner of each building within the scope of this
Article to cause a structural analysis to be made of the
building by a licensed civil or structural engineer or
licensed architect. If the building is found to be deficient
under the standards established by this Article, the owner
shall cause said building to be structurally altered so as
to conform to those standards or cause it to be demolished.
The notice or order shall be in writing and shall
be served either personally or by first class mail, return
receipt requested, upon the owner as shown in the last
equalized assessment roll, and upon the person, if any, in
apparent charge or control of the building.
The aforesaid order shall direct that the structural
analysis together with the necessary plans and calculations
be submitted to the Department for review within 270 days
after service of the order. The order shall specify that
permits required to accomplish the necessary structural
alterations shall be obtained not later than one year after
the service of the order, and that the building be corrected
to meet the minimum requirements of this Article, or be
demolished, not later than three years after such service.
The necessary alterations, however, must commence within 180
days of the date that the permit was issued.
C. APPEAL FROM ORDER. The owner or person in apparent
charge or control of the building may appeal the Director's
initial order and determination within 180 days of the
service of the aforesaid order, pursuant to the procedure
established by Chapter 3 of the Santa Ana Municipal Code.
Any such appeal shall be decided by the Hearing Officer no
later than 60 days after the date when the appeal is filed.
The order for demolition can be upheld only if, based upon
complete evidence, the Hearing Officer finds that the subject
property constitutes a nuisance and that there is no other
way reasonably to correct the nuisance.
D. RECORDATION. At the time when he serves the
ORDINANCE NO. NS-1518
Page Four
aforesaid order, the Director shall file with the Office of
the County Recorder a certificate stating that the subject
building is within the scope of Santa Ana Municipal Code,
Articte XI of Chapter 8, "Earthquake Hazard Reduction in
Existing Buildings." The certificate shall also state that
the owner thereof has been notified and ordered to structurally
analyze the building and to structurally strengthen or
demolish it where Compliance within ArticleXI is not exhibited.
If the building is either demolished, found not to
be within the scope of this Article, or is found to be
structurally capable of resisting minimum seismic forces
required by this Article, the Director shall file with the
Office of the County Recorder a certificate terminating the
status of the subject building as being classified within
the scope of Santa Ana Municipal Code, Article XI of Chapter
8, "Earthquake Hazard Reduction in Existing Buildings."
E. ENFORCEMENT. If the owner or other person in
charge and control of the subject building fails to comply
with the order within any of the time periods set forth in
Section 8-2004 (B), the Director shall order that the entire
building be vacated and that the building remain vacated
until all required analyses and structural alterations have
been completed. Whenever compliance with the aforementioned
order issued pursuant to the provisions of this Article has
not been accomplished within 90 days after the date the
building has been ordered vacated, or such additional time
as may have been granted by the Board, the Director may
order demolition of any such building in accordance with
Chapter 17 of the Santa Ana Municipal Code.
SEC. 8-2005. ANALYSIS AND DESIGN
A. GENERAL. Every structure within the scope of this
Article shall be analyzed and constructed to resist minimum
total lateral seismic forces assumed to act nonconcurrently
in the direction of each of the main axes of the structure
in accordance with the following equation:
V = IKCSW
The value of "IKCS" need not exceed the values set forth in
Table B based on the appropriate priority rating.
TABLE B
HORIZONTAL FORCE FACTORS BASED
ON RATING CLASSIFICATION
RATING
CLASSIFICATION IKCS
I 0.186
II 0.133
III & IV 0.100
B. LATERAL FORCES ON ELEMENTS OF STRUCTURES. Parts
or portions of structures shall be analyzed and designed for
lateral loads in accordance with Chapter 23 of the Uniform
Building Code but no less than the value from the following
equation:
Fp = ICpSWp
For the provision of this subsection, the product of "IS" need
not exceed the values as set forth in Table C.
ORDINANCE NO. NS-15{8~
Page Five
EXCEPTION: Unreinforced masonry walls in buildings
not having a rating classification of I may be analyzed in
accordance with Section 8-2006.
C. ANCHORAGE AND INTERCONNECTION. Anchorage and
interconnection of all parts, portions and elements of the
structure shall be analyzed and designed for lateral forces
in accordance with the equation F~ = IC~SW~ as modified by
Table C. Minimum anchorage of masonry ~al{s to each floor
or roof shall resist a minimum force of 200 pounds per
lineal foot acting normal to the wall at the level of the
floor or roof.
TABLE C
HORIZONTAL FORCE FACTORS "IS"
FOR PARTS OR PORTIONS OF STRUCTURES
RATING
CLASSIFICATION IS
I 1.50
II 1.00
III & IV 0.75
D. LEVEL OF REQUIRED REPAIR. Alterations and repairs
required to meet the provisions of this Article shall comply
with all other applicable requirements of this Code unless
specifically excluded elsewhere in this Article.
E. REQUIRED ANALYSIS.
1. CONTINUOUS STRESS PATH. A complete, continuous
stress path from every part or portion of the structure to
the ground shall be provided for the required horizontal
forces.
2. POSITIVE CONNECTIONS. Ail parts, portions or
elements of the structure shall be interconnected by positive
means.
F. ANALYSIS PROCEDURE.
(1) GENERAL. Stresses in materials and existing
construction utilized to transfer seismic forces from the
ground to parts or portions of the structure shall conform
to those permitted by the Uniform Building Code and those
materials and types of construction specified in Section
8-2006.
(2) CONNECTIONS. Materials and connectors used
for interconnection of parts and portions of the structure
shall conform to the Uniform Building Code.
(3) UNREINFORCED MASONRY WALLS. Unreinforced
masonry walls shall be analyzed to insure their capability
of resisting superimposed vertical loads in addition to the
seismic forces required by this Article.
Allowable stresses in such walls shall be obtained
by tests utilizing values established by laboratory testing
as specified in Section 8-2006E. However, no allowable
tension stress will be permitted. Walls not capable of
resisisting the applied loads shall be strengthened to
resist the forces specified in this Article or shall be
removed and replaced.
ORDINANCE NO. NS
Page Six
EXCEPTIONS:
1. Unreinforced masonry walls in buildings not
classified as a Classification Rating I may be analyzed in
accordance with the provisions of Section 8-2006.
2. Unreinforced masonry walls which carry no
design loads other than their own weight may be considered
as veneer if they are adequately anchored to new supporting
elements.
G. COMBINATION OF LOAD EFFECTS.
(1) NEW MATERIALS. Combination of load effects
shall conform to the Uniform Building Code for all new
materials introduced into the building structure to meet the
requirements of this Section.
(2) EXISTING MATERIALS. When stress in existing
lateral force resisting elements is due to a combination of
dead loads plus live loads plus seismic loads, the allowable
working stress specified in the Code may be increased 100%.
However, no increase shall be permitted in the stresses
allowed in Section 8-2006 of this Article and the stresses
in members due only to seismic and dead loads shall not
exceed the values permitted by Chapter 23 of the Uniform
Building Code.
(3) ALLOWABLE REDUCTION OF BENDING STRESS BY
VERTICAL LOAD. In calculating maximum tensile stress due to
earthquake forces, the maximum tensile fiber stresses may be
reduced by not more than 50 percent of the direct stress due
to vertical dead loads.
SEC. 8-2006. MATERIALS OF CONSTRUCTION
A. GENERAL. Ail materials permitted by this Code
including their appropriate allowable stresses and those
existing configurations of materials specified herein may be
utilized to meet the requirements of this Article.
B. EXISTING MATERIALS.
(1) UNREINFORCED MASONRY WALLS. Unreinforced
masonry walls analyzed in accordance with this Section may
provide vertical support for roof and floor construction and
resistance to lateral loads.
Tension stresses due to seismic forces normal to
the wall may be neglected if the wall does not exceed the
height or length to thickness ratio and the in-plane shear
stresses due to seismic loads as set forth in Table D.
ORDINANCE NO. NS ~518
Page Seven
TABLE D
ALLOWABLE VALUE OF
UNREINFORCED MASONRY WALL~I~
WITH MINIMUM QUALITY MORTAR'-'
RATING
CLASSIFICATION
MAXIMUM RATIO
UNSUPPORTED
HEIGHT OR LENGTH
TO THICKNESS
SEISMIC IN-PLANE
SHEAR STRESS
BASED ON GROSS AREA
I NOt applicable(2) Not applicable(2)
II 9 3 psi(3)
III 10 3 psi(3)
IV 12 3 psi(3)
FOOTNOTES: (1) Minimum quality mortar shall be determined
by laboratory testing in accordance with Section 8-2005 F.
(2) Walls of buildings within rating classification I shall
be analyzed in accordance with Section 8-2005 F. (3) Allowable
shear stress may be increased by the addition of 10% of the
direct stress due to the weight of the wall directly above.
The wall height or length may be measured horizontally to
supporting elements providing the stiffness of the supporting
member is at least twice as stiff as the tributary wall.
Stiffness shall be based on the gross section.
(2) EXISTING ROOF, FLOORS, WALLS, FOOTINGS, AND
WOOD FRAMING. Existing materials utilized in the described
configuration may be used as part of the lateral load resisting
system, provided that the stresses in these materials do not
exceed the values shown in Table E.
TABLE E
VALUES FOR EXISTING MATERIALS
MATERIALS(2) ALLOWABLE VALUES
HORIZONTAL DIAPHRAGMS
(a) Roofs with straight
sheathing and roofing
applied directly to the
sheathing.
150 lbs. per foot for
seismic shear.
(b) Roofs with diagonal
sheathing and roofing
applied directly to the
sheathing.
400 lbs. per foot for
seismic shear.
(c) Floors with straight
tongue and groove sheathing
150 lbs. per foot for
seismic shear.
(d) Floors with straight
sheathing and finished
wood flooring.
300 lbs. per foot for
seismic shear.
(e) Floors with diagonal
sheathing and finished
wood flooring.
400 lbs. per foot for
seismic shear.
(f) Floors or roofs with
straight sheathing and
plaster applied t~l~he
joist or rafters.
Add 50 lbs. per foot
to materials la and lc.
ORDINANCE NO. NS~1518
Page Eight
2. SHEAR WALLS
(a) Wood stud walls with
wood lath and plaster.
50 lbs. per foot each
side for seismic shear.
(b) Wood stud walls with
plaster and lath other
than wood lath.
100 lbs. per foot each
side for seismic shear.
PLAIN CONCRETE FOOTINGS
f' = 1500 psi unless
otherwise shown by tests.
4. DOUGLAS FIR WOOD Allowable stress same as
No. 1 (d)- (f)
REINFORCING STEEL
f. = 20f000 lbs per
s~uare ~nch maximum.
STRUCTURAL STEEL
f~ = 20,000 lbs. per
s~uare inch maximum.
FOOTNOTES: (1) The wood lath and plaster must be reattached
to existing joists or rafters in a manner approved by the
Department. (2) Material must be sound and in good condition.
C. STRENGTHENING OF EXISTING MATERIALS.
New materials may be utilized to strengthen portions
of the existing seismic resisting system in the described
configurations provided that the stresses do not exceed the
values shown in Table F.
TABLE F
ALLOWABLE VALUES OF NEW MATERIALS USED
IN CONJUNCTION WITH EXISTING CONSTRUCTION
NEW MATERIALS
ALLOWABLE VALUES
Plywood sheathing applied directly
over existing straight sheathing
with ends of plywood sheets bearing
on joists or rafters and edges of
plywood located on center of individual
sheathing boards.
Same as specified
in U.B.C. Table 25-J
for blocked diaphragms.
2. SHEAR WALLS '
a. Plywood sheathing applied directly
over existing wood studs. No value
shall be given to plywood applied over
existing plaster or wood sheathing.
Same as specified
in U.B.C. Table
25-K for shear
walls.
b. Dry wall or plaster applied directly
over existing wood studs.
Same as specified
in U.B.C. Table
47-I.
c. Dry wall or plaster applied to
plywood sheathing over existing
wood studs.
33 1/3 per cent of
the values specified
in U.B.C. Table 47-I.
e
Shear bolts and shear dowels embedded
a minimum of 8 inches into unreinforced
masonry walls. Bolt centered in a 2 1/2
inch diameter hole with dry-pack or non-
shrink grout around circumference of
bolt or dowel. (1)
Same as value given
for solid masonry in
U.B.C Table 24-G.
Max. 750 lbs.
ORDIN~/qCE NO. NS-15'18
Page Nine
4e
Se
Tension bolts and tension dowels ex-
tending entirely through unreinforced
masonry walls secured with bearing plates
on far side of wall with at least 30 sq.
inches of area.(2)
1200 lbs.
per bolt.
Reinforced masonry infilled openings in
existing unreinforced masonry walls with
dowels to match reinforcing.
Same value as for un-
reinforced masonry
walls.
e
e
Masonry piers and walls reinforced per
U.B.C. SectiOn 2418 and designed for
tributary loads.
Concrete footings, walls and piers
reinforced as specified in
Chapter 26 and designed for
tributary loads.
Foundation pressures for
structures exhibiting no
evidence of settlement.
FOOTNOTES:
in Section 8-2006.
minimum in diameter.
(1) Bolts and dowels to be tested as
(2)
Same values as speci-
fied in U.B.C. Table
24-H.
same values as speci,
fied in U.B.C.
Chapter 26.
Calculated existing
foundation pressure
due to max dead load
plus live load may be
increased 25% for dead
load, and may be in-
creased 50% for dead ~
load plus seismic load.
specified
Bolts and dowels to be 1/2 inch
D. ALTERNATE MATERIALS. Alternate materials and
methods of construction may be approved by the Department in
accordance with the provisions of Section 106 of the Uniform
Building Code. ("U.B.C.")
E. MINIMUM ACCEPTABLE QUALITY OF EXISTING UNREINFORCED
MASONRY WALLS.
(1) GENERAL PROVISIONS. Ail unreinforced masonry
walls utilized to carry vertical loads and seismic forces
parallel and perpendicular to the wall plans shall be tested
as specified in this Section. All masonry quality shall
equal or exceed the minimum standards established herein or
shall be removed and replaced by new materials. Alternate
methods of testing approved by the Department may be used.
Nothing shall prevent point with cement mortar of all the
masonry wall joints before the tests are first made. If the
exterior joints are pointed then the inside face must also
be pointed. Prior to any pointing, the wall surface must be
sand or water blasted to remove loose and deteriorating
mortar. All preparation and cement mortar pointing shall be
done under the continuous inspection of the Director with a
subsequent written report to the Department. All testing
shall be performed by an approved testing agency in accordance
with the requirements specified in this Subsection.
EXCEPTION: Unreinforced masonry walls which carry
no design horizontal or vertical loads other than their own
weight may be considered as veneer if they are adequately
anchored to new supporting elements.
(2) NUMBER AND LOCATION OF TESTS. The quality of
mortar in all masonry walls shall be determined by performing
in place shear tests or by testing eight inch diameter
ORDINANCE NO. NS-1518
Page Ten
cores. The minimum number of tests shall be two per wall or
line of wall elements resisting a common seismic force, 1
per 1500 square foot of wall surface, or eight minimum
whichever requires the largest number of tests or cores.
The exact test or core location shall be determined at the
building site by the licensed engineer or architect responsible
for the seismic analysis of the subject building. The
results of all tests or coring shall be recorded and reported.
(3) IN PLACE SHEAR TESTS. The bed joints of the
outer wythe of the masonry shall be tested in shear by
laterally displaying a single brick relative to the adjacent
bricks in that wythe. The opposite head joint of the brick
to be tested shall be removed and cleaned prior to testing.
The minimum quality mortar in 80 percent of the shear tests
shall not be less than the total of 30 psi plus the axial
stress in the wall at the point of the test. The shear
stress shall be based on the gross area of both bed joints
and shall be that at which movement of the brick is first
observed.
(4) CORE TESTS. A minimum number of mortar test
specimens equal to the number of required cores shall be
prepared from the cores and tested as specified herein. The
mortar joint of the outer wythe of the masonry core shall be
tested in shear by placing the circular core section in a
compression testing machine with the mortar bed joint rotated
15 degrees from the axis of the applied load. The mortar
joint tested in shear shall have an average ultimate stress
based on the gross area of 20 psi. The average shall be
made from the total number of cores made. If test specimens
cannot be made from the total taken the shear value shall be
reported as zero. The results of all coring and shear
testing shall be reported.
F. TESTING OF SHEAR BOLTS. One-fourth of all new
shear bolts and dowels embedded in unreinforced masonry
walls shall be tested by the Director using a torque calibrated
wrench to the following minimum torques:
1/2" diameter bolts or dowels = 40 foot-lbs.
5/8" diameter bolts or dowels = 50 foot-lbs.
3/4" diameter bolts or dowels = 60 foot-lbs.
No bolts exceeding 3/4' shall be used. Ail nuts
shall be installed over malleable iron or plate washers when
bearing on wood and heavy cut washers when bearing on steel.
G. DETERMINATION OF ALLOWABLE STRESSES FOR DESIGN METHODS
BASED ON TEST RESULTS.
(1) DESIGN SHEAR VALUES. Design seismic in-plane
shear stresses greater than permitted in Table D shall be
substantiated by tests performed as specified in Section
8-2006 E (3) and (4).
Design stresses shall be related to test results
obtained as noted in Table G. Intermediate values below the
maximum may be interpolated.
ORDINANCE NO. NS &I518
Page Eleven
TABLE G
ALLOWABLE SHEAR STRESS FOR TESTED
UNREINFORCED MASONRY WALLS
Eighty percent
by test results
in psi not less
than
Average test results
cores in psi
30 plus axial stress
40 plus axial stress
50 plus axial stress
or more
FOOTNOTE: (1)Allowable
addition of 10% of the axial
wall directly above.
Seismic in-plane
shear based on
gross area
20
2.6.7
33.3
or more
-si(1)
3 ~ . (1)
4 ~ps .~ (1)
5 ps~- -
shear stress may be increased by
stress due to the weight of the
(2) DESIGN COMPRESSION AND TENSION VALUES.
Design compressive stresses of analysis specified in this
section shall be 100 psi. Design tension values for unrein-
forced masonry shall be assumed equal to zero.
SEC. 8-2007. INFORMATION REQUIRED ON PLANS
A. GENERAL. In addition to the seismic analysis
required elsewhere in this Division, the licensed engineer
or architect responsible for the seismic analysis of the
subject building shall determine and record the information
required by this Section on the approved plans.
B. CONSTRUCTION DETAILS. The following construction
details shall be made part of the approved plans:
(1) Ail unreinforced masonry walls shall be
anchored with tension bolts through the wall or by existing
rod anchors at a maximum anchor spacing of six feet to all
floors and roofs. Ail existing rod anchors shall be secured
to joists or rafters by bolting to develop the required
forces. The Department may require testing to verify
adequacy of embedded ends of existing rod anchors.
(2) Diaphragm chord stresses of horizontal dia-
phragms shall be developed in existing materials or by
addition of new materials.
(3) Where wood roof or floor members other than
rafters or joists are supported in masonry pockets, ledgers
or columns shall be installed to support vertical loads of
the roof or floor members.
(4) Parapets and exterior wall appendages not
capable of resisting the forces specified in this Article
shall be removed, stabilized or braced to insure that the
parapets and appendages remain in their original position.
(5) All deteriorated mortar joints in unreinforced
masonry walls shall be pointed with cement mortar. Prior to
any pointing, the wall surface must be sand or water blasted
to remove loose and deteriorated mortar. All preparation
and pointing shall be done under the continuous inspection
of the Director with a subsequent written report to the
Department.
ORDINANCE NO. NS-151~
Page Twelve
C. EXISTING CONSTRUCTION. The following existing
construction information shall be made part of the approved
plans:
(1) The approximate age of building.
(2) The typical footing width, depth and maximum
soil bearing for dead plus live loads.
(3) The type and dimensions of existing walls and
the size and spacing of floor and roof members.
(4) The extent and type of existing wall anchorage
to floors and roof.
(5) Accurately dimensioned floor plans and masonry
wall elevations showing dimensioned openings, piers, wall
thickness and heights.
(6) The type of interior wall surfaces and if
reinstalling or anchoring of ceiling plaster is necessary.
ADOPTED this 19th
1980, by the following vote:
day of February ,
AYES: COUNCILMEN: Bricken, Griset, Luxembourger,
Markel, Serrato, Ward, Yamamoto
NOES: COUNCILMEN: None
ABSENT: COUNCILMEN: None
ATTEST:
CITY ATTORNEY