Loading...
HomeMy WebLinkAboutNS-2192 - Amending Chapter 14 of the Santa Ana Municipal Code to Adopt the 1991 Edition of the Uniform Fire CodeO74 ORDINANCE NO. NS- 2192 AN ORDINANCE OF THE CITY OF SANTA ANA AMENDING CHAPTER 14 OF THE SANTA ANA MUNICIPAL CODE TO ADOPT THE 1991 EDITION OF THE UNIFORM FIRE CODE THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES ORDAIN AS FOLLOWS: SECTION 1: That Section 14-1 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 14-1. Adoption of the Uniform Fire Code, 1991 Edition. There is hereby adopted by the city of Santa Aha that certain code known as the "Uniform Fire Code, 1991 Edition," and the whole thereof including the Appendices therein, and the accompanying Uniform Fire Code Standards, save and except such portions as are hereinafter deleted or amended, of which code not less than one (1) copy has been and is now on file in the office of the clerk of the council of the city of Santa Aha. The said code is adopted and incorporated as fully as if set forth at length herein and, subject to all amendments set forth in this article, shall be in effect within the City of Santa Aha from the effective date of this article. Any provision of this article amending the Uniform Fire Code shall be construed as amending the 1991 Edition thereof including such provisions enacted prior to this adoption of the said 1991 Edition and not thereafter repealed. The said Uniform Fire Code, 1991 Edition, as thus amended, together with all other provisions of this article, shall be known as the "Fire Code of the city of Santa Ana." SECTION 2: That Section 14-17 of the Santa Ana Municipal Code is hereby repealed. SECTION 3: That Section 14-25 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 14-25. Access roadways for apparatus (Section 10.204). Section 10.204 of the Uniform Fire Code is amended to read as follows: (a) Required construction. Every building or portions of buildings hereafter constructed shall have fire apparatus access roadways. Such access roadways shall provide two (2) 075 0RD A cE s-2192 Page 2 separate but interconnected means of ingress and egress. Access shall be at least twenty (20) feet in clear width. A forty-foot outside and twenty-foot inside radius shall be provided wherever they make a turn. The total width shall be continuously paved to accommodate forty thousand (40,000) pounds and shall not exceed the angle of departure (eight (8) degrees or fourteen (14) per cent) for fire apparatus on any slope. Access roadways shall have a vertical clearance of not less than thirteen (13) feet six (6) inches above the finished driveway surface. EXCEPTIONS: When buildings are completely protected with an approved automatic fire sprink'ler system, the provisions of this section may be modified. When access roadways cannot be installed due to topography, waterways, nonnegotiable grades or other similar conditions, the chief may require additional fire protection as specified in Section lO.301(b). When there are not more than two (2) Group R, Division 3 or Group M Occupancies, the requirements of this section may be modified, provided, in the opinion of the chief, firefighting or rescue operations would not be impaired. (b) Required markings. Any owner or occupant of a private parking area, including, but not limited to, private streets or roadways, driveways, off-street parking facilities, alleys, parking lots and any other nonpublic place where vehicles of any type or kind are intended to be or are often found, must: (1) Post emergency fire lane signs as directed in subsection (C), or (2) Paint appropriate curbs or pavement in red paint pursuant to subsection (d) and as directed by the fire chief or his designated representative. (c) Signs. The fire chief or his designated representative may direct the owner or occupant of the area described in subsection (b) as to the location that said signs must be posted by said owner or occupant. If not so directed, the said owner or occupant must post signs in an obvious, conspicuous location immediately adjacent to, and visible from, the designated fire lane clearly stating in letters not less than one (1) inch in height that the area is a fire lane. (d) Paint. Ail painting to be performed as described in subsection (b) shall consist of outlining or painting the ordinance NS-2192 Page 3 076 designated fire lane in red and, in contrasting color, marking the place with the words "FIRE LANE" which are clearly visible from a vehicle, or by painting a red curb or red paint on the edge of the roadway upon which is clearly marked the words "FIRE LANE." (e) (1) Obstructing emergency access lane. The required width of any fire apparatus access road shall not be obstructed in any manner. Minimum required widths and clearances established under this section shall be maintained at all times. (2) (3) No person shall cause or permit any vehicle, including, but not limited to, automobile, motorcycle, truck, bicycle or any other vehicle in his control or ownership, to be stopped in an area designated for emergency vehicles. This section applies to all nonemergency vehicles whatsoever, attended or unattended, stopped for any length of time except when necessary to avoid conflict with other traffic or in compliance with directions of a police officer or fireman. (4) Any vehicle found in violation of this section may be towed at the owner's or operator's expense at the request of any Santa Ana police officer, parking control officer, California Highway Patrol officer, Orange County deputy sheriff or any fire department personnel described in section 1-18 of this Code. (f) Extent. The access roadway shall be extended to within one hundred fifty (150) feet of all portions of the exterior walls of the first story of any building. Where the access roadway cannot be provided, approved fire protection system or systems shall be provided as requiredand approved by the fire marshal. (g) Fire protection alternate. Where fire protection systems approved by the fire marshal are provided, the above required clearance may be modified. (h) Oversizing. The fire marshal shall have the authority to require an increase in the minimum access width where such width is not adequate for fire or rescue operations. (i) Bridges. Where a bridge is required to be used as access under this section, it shall be constructed and maintained in accordance with the applicable sections of the ORDINANCE NS-2192 Page 4 building code and using design live loading sufficient to carry the imposed loads of the fire apparatus. (j) Misdemeanor violations. Any violation of subsections (b), (c) or (d) of this section shall be deemed a misdemeanor. (k) Infraction violations. Any violation of subsection (e) of this section shall be deemed an infraction. SECTION 4: That Section 14-27 of the Santa Aha Municipal Code is hereby amended to read as follows: Sec. 14-27. Building height regulation (Section 10.207). Section 10.207 is added to the U~iform Fire Code, to read as follows: Section 10.207. No building shall hereafter be constructed which exceeds fifty-five (55) feet in height, measured from the pavement surface of fire department vehicular access to the top of the floor surface of the for human occupancy, unless either: (b) highest story designed (a) The building complies with all the standards and regulations adopted pursuant to Chapter 3 of Part 2 of Division 12 of the Health and Safety Code of the State of California for a new highrise structure, as defined in Section 13210 of the said Health and Safety Code; or The building is accessible to fire department laddering equipment and overhead hose streams on at least two (2) sides, the height of which do not exceed the laddering capability of the fire department. SECTION 5: That Section 14-30 of the Santa Ana Municipal Code is hereby amended to read as follows: Bec. 14-30. Installations of automatic sprinkler (Section 10.501(b)). systems Section 10.501, subsection (b), of the Unifor~ Fire Code is amended by adding to said subsection the following paragraphs: An automatic sprinkler system must be installed in buildings hereafter constructed, or when additions, alterations, or repairs are such as to require the building to comply with all the requirements of the building code of the OP/)INANCE NS-2192 Page 5 city of Santa Ana for new buildings, in either of the following circumstances: (a) (b) The building would require a fire flow of more than three thousand five hundred (3,500) gallons per minute if such system were not installed; The building exceeds two (2) stories in height, unless the building is designed for Group R occupancies, as defined in the building code of the city of Santa Ana, or is a building or structure accessory thereto. EXCEPTION: Open, freestanding parking structures, whether or not such structures exceed two (2) stories in height, constructed of noncombustible materials above grade, and meeting all of the provisions of the building code of the city of Santa Ana and National Fire Protection Association Standard 88A, need not be provided with automatic fire sprinklers unless such sprinklers would be required due to the area and height limitations of the building code of the city of Santa Ana, Table No. 7A, Chapter 38, or the estimated fire flow exceeds five thousand five hundred (5,500) gallons per minute. Where a conflict exists between the building code of the City of Santa Ana and National Fire Protection Association Standard No. 88A, the more restrictive requirements shall apply. An automatic sprinkler system must be installed in any portion of a building, whether newly constructed or preexisting, in or into which either of the following uses is initiated or expanded: (a) A place of public assemblage which provides for the gathering together of one hundred (100) or more persons, for such purposes as deliberation, education, instruction, worship activities, entertainment, amusement, or the awaiting of transportation, or in a dining or drinking establishment; (b) A Group H Occupancy, as defined in the building code of the City of Santa Ana. All sprinkler systems shall have the Fire Department pumper connection located at the property line, on the address side of the building as close as practical to the public hydrant. '078 5 079 ORDINANCE NS-2192 Page 6 SECTION 6: That Section 14-31 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 14-31. Fire flow requirements (Section 10-401). Section 10.401 of the Uniform Fire Code is amended to read as follows: No building shall hereafter be constructed which would require a fire flow of more than five thousand five hundred (5,500) gallons per minute. No existing building shall be added to, altered, or changed in the character of its occupancy so as to increase its required fire flow above five thousand five hundred (5,500) gallons per minute. No existing building which currently requires a fire flow of more than five thousand five hundred (5,500) gallons per minute shall be added to, altered, or changed in the character of its occupancy if such addition, alteration, or change would increase the fire flow required for such building. No building shall hereafter be ~onstructed, and no additions, alterations, or repairs shall be made to an existing building within any twelve-month period which exceed twenty-five (25) per cent of its value, and no existing building shall be changed in the character of its occupancy so as to increase the fire flow required for such building, unless fire hydrants and appurtenant water supply capable of delivering the fire flow that will be required for such building, with a residual pressure measured at the hydrant outlet of not less than twenty (20) pounds per square inch during times of average daily consumption, are located in accordance with the following distance limitations: In any case where this requirement applies solely by reason of additions, alterations, or repairs to an existing building; and in the case of new construction of a building designed for Group R, Division 3 occupancy, as defined in the building code of the city of Santa Ana, or building or structure accessory thereto: the required hydrant or hydrants must be located within five hundred (500) feet of all portions of the exterior walls of the building or be protected. Such required hydrant or hydrants may be located either on a public street or on the site of the premises to be protected. In all other cases: The required hydrant or hydrants shall be located on the site of the premises to be protected, except that any required hydrant may be located on a public street if such location is within one hundred fifty (150) feet of all portions of the exterior walls of the building to be protected. ORDINANCE NS-21q'2 080 Page 7 Where more than one fire hydrant is located on the site of the premises to be protected, or where a combination of hydrants located on such site and a public street are used to meet the distance requirements, the required fire flow in gallons per minute may be divided between such hydrants provided: 1. That the combination of hydrants will deliver the required flow, and 2. That no single hydrant has a flow of less than one thousand five hundred (1,500) gallons per minute with a residual pressure measured at the hydrant outlet of not less than twenty (20) pounds per square inch during times of average daily consumption. Water supply may consist of reservoirs, pressure tanks, elevated tanks, water mains, or other fixed system capable of supplying the required fire flow, subject to the approval of the fire marshal. The precise location, number and type of fire hydrants connected to a water supply to be provided in accordance with this subsection shall be subject to the approval of the fire marshal. All hydrants shall be accessible to the fire department apparatus by roadways meeting the requirements of Section 10.204. No use of an existing building, or any portion thereof, for either a place of assemblage or a Group H occupancy, as defined in subsections (a) and (b) of this section, shall be initiated or expanded unless the building as a whole will comply with the requirements of this subsection (c) such as would apply to the new construction of such building for the same uses. SECTION 7: That Section 14-32 of the Santa Ana Municipal Code is hereby amended to read as follows: sec. 14-32. Valuation of existing buildings (Section 10.207). Section 10.207 is added to the Uniform Fire Code to read as follows: For purposes of this section, an existing building or structure shall be deemed to have a value equal to the current cost of construction of a building or structure of the same size and type of construction. In determining such value, the fire marshal shall be guided by the most recent building valuation data published by the International Conference of Building officials. 081 ORDINANCE Page 8 SECTION 8: That Section 14-33 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 14-33. Determination of require4 fire flow (Section 10.401(b)). The text of Section 10.401 as it appears in the Uniform Fire Code is designated as Subsection (a) of Section 10.401 and Subsection (b) is added to Section 10.401 of the Uniform Fire Code to read as follows: (b) In determining the fire flow requirements for any building, structure, or fire area, the fire marshal shall proceed in accordance with the standards set forth in that certain "Santa Ana Fire Department Guide for Determination of Fire Flows," of which not less than one (1) copy is on file in the office of the clerk of the council of the City of Santa Aha. SECTION 9: That Section 14-34 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 14-34. Historical property (Section 10.401(c)). Subsection (c) is added to Section 10.401 of the Uniform Fire Code to read as follows: (c) (~) (2) (3) This subsection applies only to buildings, or portions thereof, which have been designated as historical property pursuant to section 30-1 of the Santa Ana Municipal Code, and which would require either the installation of an automatic sprinkler system, or the installation of one or more fire hydrants with appurtenant water supply, or both, in order to comply with this section, by reason of the additions, alterations or repairs or changes of occupancy proposed for such building. An automatic sprinkler system shall be installed in any portion of such building which is to be used as a place of public assemblage or a Group H occupancy, as defined in the building code of the City of Santa Ana. Subject to the overriding requirement of paragraph (2) of this subsection, changes to buildings within the scope of this section shall be subject to approval on the following standard: Installations of automatic sprinkler systems or fire hydrants shall be required only to the extent necessary to avoid an increase in the risk of fire occurring, 8 Page 9 (4) the danger to life in the event of fire, or the difficulty of fire suppression or to avoid a prolongation of any especially hazardous situation. The need of such installations or alternative fire protection requirements shall be evaluated in view of any modifications in building safety standards due to application of the state historical buildings code, and the fire marshal shall coordinate his review with that of the building official in this regard. The fire marshal may impose alternative fire protection requirements on building changes within the scope of this section as appropriate to maintain this standard and shall waive any requirement of this section which is inconsistent therewith. The fire marshal shall give priority to building changes within the scope of this section which are submitted for his review by the community redevelopment agency. SECTION 10: That Section 14-38 of the Santa Ana Municipal Code is hereby amended to read as follows: sec. 14-38. Accidental alarms (Section 13.204). Section 13.204 is added to the Uniform Fire Code, to read as follows: Section 13.204. (a) As used herein, the following terms shall have the following meanings: "accidental alarm" means an alarm, message, signal, or notice received by the fire department as a result of the failure of a fire alarm system to function properly. "manually activated alarm system" means a non-residential alarm system which is activated while the business is open and/or occupied and activated by the deliberate acts of an employee, or a residential alarm system designed to be activated by a tenant from within a residential unit. It does not include manual pull stations activated from areas accessible to the public. "automatic alarm system" means an alarm system other than a manually activated alarm system. It does not include manual pull stations activated from areas accessible to the public. (b) When accidental alarms are received by the fire 9 Pane 10 department, the fire chief is authorized to demand that the user of the responsible fire alarm system correct, replace, or disconnect such system. (c) Except as otherwise provided in subsection (d) of this section, any person having an alarm system which results in a fire department response in which the alarm proves to be an accidental alarm shall pay a penalty assessment fee to the city as follows: (1) Accidental alarms received by the city fire department from automatic alarm systems which are in excess of the maximum allowable number, as set forth in paragraph (3) of this subsection, shall result in an automatic alarm penalty assessment in such amount as shall be set by resolution of the city council. (2) Alarms from manually activated alarm systems which are in excess of the maximum allowable number of false alarms, as set forth in paragraph (3) of this subsection, shall result ~n a manually activated alarm penalty assessment in such amount as shall be set by resolution of the city council. (3) Penalty assessments shall be made for accidental alarms which number more than one (1) in any thirty-day period; or more than two (2) within any ninety-day period; or more than three (3) within any one-year period. (d) Commencing with the date of a new alarm installation and continuing until the date six (6) months thereafter, or until there have been three accidental alarms from such new alarm installation, whichever first occurs, subsection (c) of this section shall not apply to accidental alarms from such new alarm installation. (e) The fire chief reserves the right to discontinue response by fire department personnel to any location of a silent or audible alarm when: (1) The alarm user has been given written notice and assessed six (6) penalty assessments within a one-year period; or (2) The alarm user has failed to pay any such penalty assessment. Reinstatement may occur when the alarm user has taken steps to eliminate or correct the problem(s) and has documented the corrective action in writing to the fire chief. 10 ORDINANCE NS-21 '2 08'4 Page 11 ~: That Section 14-40 of the Santa Ana Municipal Code is hereby amended to read as follows: seo. X4-40. Building maintenance and housekeeping (Article 11, Division VII). Article 11 of the Uniform Fire Code is amended by adding Division VII, consisting of Sections 11.701 and 11.702, thereto, to read as follows: DIVISION VII. BUILDING MAINTENANCE AND HOUSEKEEPING Building Maintenance. Section 11.701. All buildings and premises shall be maintained in good repair, free from any condition that presents a fire hazard or any condition which would add to or contribute to the rapid spread of fire. Housekeeping. Section 11.702. Ail buildings and premises shall be maintained in good repair and in a clean and orderly manner. Provisions shall be made for the proper storage and disposal of waste materials and rubbish consistent with the following: (a) (b) Ail basements, cellars, floors, closets, attics and other similar places not open to continuous observation, shall be kept free from combustible litter and rubbish at all times. All combustible waste material and rubbish shall be stored in approved noncombustible containers or receptacles, or consistent with approved fire prevention practice, until such time as such waste material is removed from the premises or otherwise properly disposed of. All such waste containers, other than convenience waste receptacles emptied at the close of each day, shall be provided with tightfitting, noncombustible covers. SECTION 12: That the Santa Ana Municipal Code is hereby amended by adding a section, to be numbered 14-48, which said section reads as follows: Bec. 14-48. Fireworks (Beotion 78.202). Section 78.202 of the Uniform Fire Code is amended to read as follows: Sec. 78.202. The storage, use and handling of fireworks 11 ORDINANCE NS-2192 Page 12 is prohibited. RXCEPTIONB: 1. Storage and handling of fireworks is allowed aa aet forth in Article 77. 2. The use of fireworks for display ia allowed as set forth in Section 78.203. 3. The use of State Fire Marehal approved Safe-and-Sane Fireworks is allowed as regulated by Article II (commencing with section 14-51) of Chapter 14 of the Santa Aha Municipal Code. SECTION Code is hereby amended to read as follows: Bec. 14-49. Deletions from Uniform Fire Code. The following parts of the Uniform Fire Code deleted: Appendix II-C Appendix III-A; Appendix III-B; Appendix VI-C. 13: That Section 14-49 of the Santa Ana Municipal are hereby SECTION 14: If any section, subsection, sentence, clause, phrase or portion of this ordinance is for any reason held to be invalid or unconstitutional by the decision of any court of competent jurisdiction, such decision shall not affect the validity of the remaining portions of this ordinance. The City Council of the City of Santa Ana hereby declares that it would have adopted this ordinance and each section, subsection, sentence, clause, phrase or portion thereof irrespective of the fact that any one or more sections, subsections, sentences, clauses, phrases, or portions be dec].ared invalid or unconstitutional. SECTION 15: Neither the adoption of this ordinance nor the repeal hereby of any ordinance shall in any manner affect the prosecution for violation of ordinances, which violations were committed prior to the effective date hereof, nor be construed as affecting any of the provisions of such ordinance relating to the collection of any such license or penalty or the penal provision applicable to any violation thereof, nor to affect the validity of any bond or cash deposit in lieu thereof, required to be posted, filed or deposited pursuant to any ordinance and all rights and obligations thereunder appertaining shall continue in full force and effect. 12 ORDINANCE NS-2192 Page 13 ADOPTED this 20th day of ATTEST: COUNCILMEMBERS: Young Aye Pulido Aye Lutz Aye Mills Aye Moreno Aye Norton Aye Richardson Aye ""086 April , 1993. Young~ / APPROVED AS TO FORM: Edward J.'C~ city Attorney CERTIFICATE OF ORIGINALITY & PUBLICATION State of California County of Orange I, JANICE C. GUY, Clerk of the Council, do hereby certify the attached Ordinance NS-~/~-~ to be the original ordinance adopted by the City Council of the City of Santa Ana on ~--ff-~3 ; and that said ordinance was published in accordance with the Charter of the city of Santa Aha. ~l~of the Council, Dat city of Santa Ana