Laserfiche WebLink
Equipment: Panel IC Location: Fed from SWBD MSB <br />Description Recommendation <br />Panel IC has a front cover which is not Due to current condition of panelboard IC, <br />properly secured to the enclosure box and panelboard shall be replaced with new <br />does not comply with manufacturer's panelboard with same ratings, voltage, <br />recommended securing methods. The amperage, phase, and AIC rating. <br />panelboard also lacks proper breaker <br />space covers plates and is in violation of <br />NEC 110.27 Guarding from Live Parts. <br />o Short circuit analysis: this section presents all the information regarding the <br />device duty calculation, a brief methodology of short circuit calculation per <br />IEEE/ANSI standards including the tabular format of the scenarios and <br />results along with the supportive notes. <br />o Protective device coordination study: this section includes the information <br />regarding the device coordination, a brief methodology per standards, list of <br />all the TCCs, TCC graphs, and device settings in tabular format with <br />adjustable settings for low and medium voltage devices. <br />o Arc flash study: this section includes the information regarding the arc flash <br />study, a brief methodology per standards, list of all the scenarios, and a <br />tabular format of the incident energy results. <br />o System data: this section reflects all the resources and documentations <br />utilized for the study for equipment, data gathering and modeling including <br />the assumptions. <br />o Utility data: fault current information obtained from the utility for the purpose <br />of study for each model. <br />