CITY OF SANTA ANA <br /> SPECIFICATIONS <br /> PROJECT NO.: 25-6030 <br /> TRAFFIC SIGNAL INSTALLATION AT SEGERSTROM AVENUE AND ROSEWOOD <br /> AVENUE <br /> If a conduit is bored or jacked across existing sewer mains or laterals, the contractor shall <br /> conform to the following requirements: <br /> 1. Pothole to determine location and depth of the sewer mains and laterals. <br /> 2. Visual confirmation by City Inspector shall be done during the boring/jacking of <br /> the conduit across the sewer mains or laterals for any damages prior to back filling <br /> the pothole. <br /> 3. If visual confirmation is not done,the contractor shall perform Video Inspection of <br /> Sewer Mains and Laterals per the following specifications. <br /> a. Video Inspection of Sewer Mains and Laterals <br /> The contractor shall use CCTV equipment to verify that City sanitary sewer <br /> mains have not been impacted. This includes all mains that appear on the plan <br /> of construction drawings as possible points of interference, regardless of the <br /> relative elevation of the sewer and what is believed to be the elevation of the <br /> newly constructed facility. <br /> The contractor shall use equipment specially designed and constructed for <br /> sewer inspection and televising. The camera must have light sources of suitable <br /> illumination output to provide a clear picture of the entire periphery of pipe. <br /> The camera must be able to be rotated to a position that will assure that the total <br /> periphery of the sewer is in focus at all times, regardless of the diameter of the <br /> pipe being inspected. The camera, transport system, and other components of <br /> the video system shall be capable of producing a picture adequate for the <br /> purposes of the inspection as stated herein. Video runs showing condensation <br /> or submersion of the lens,poor or out-of-focus images,poor audio,or otherwise <br /> poor image quality shall be cause for rejection and may necessitate re-televising <br /> at the consultant's expense if the City determines the video run is not of <br /> acceptable quality. <br /> A cable footage counter, accurate to within one (1) foot in 1000 feet, shall be <br /> used and shall be indicated on the monitor and recorded on the video. The date <br /> of inspection, continuous forward and reverse readout of camera distance from <br /> referenced access hole, the City supplied upstream and downstream <br /> manhole identification number with an arrow indicating the direction of flow, <br /> the size of the pipe, the name of the street, the time of day and the project or <br /> location name as supplied by the City shall be displayed continuously on the <br /> monitor and recorded on the video. The use of non-standard or incorrectly <br /> numbered manholes by the contractor on the video overlay is cause for <br /> rejection of the digital video and any costs associated with re-videoing of <br /> the main that are necessitated by the contractor's failure to use designated <br /> naming conventions will be borne entirely by the contractor. The footage <br /> relative to the center of the manhole at the start of each run shall be set to <br /> accurately reflect a center of manhole starting position of 0.00 feet regardless <br /> of where along the pipe and at what footage the run begins. All video operations <br /> 65 <br />