Laserfiche WebLink
CODE <br /> <br />The elevator equipment shall be furnished and installed in accordance with ASME / ANSI <br />A17.1 Safety Code for Elevators and Escalators, An American National Standard. including <br />the latest Supplement, and the Americans with Disabilities Act. <br /> <br />COOE~OCAL) <br /> <br />The elevator equipment shall comply with all applicable local codes. <br /> <br />WORK BY OTHERS <br /> <br />The following items must be performed by others and you agree to: <br /> <br />Provide suitable ventilation and cooling equipment, if required, to maintain the machine <br />room temperature between 45 degree F and 90 degree F. The relative humidity should not <br />exceed 85 percem non-condensing. <br /> <br />Provide electrical power for light, tools, hoists, etc. during installation as well as electric <br />current for starting, testing and adjusting the elevator. <br /> <br />Provide a smoke detector system, located as required with wiring from the sensing devices <br />to each elevator controller. <br /> <br />Do any cutting, including cut outs to acconu-aodate ball signal fixtures, patching and <br />painting &walls, floors or partitions. <br /> <br />Provide a fused d~sconnect switch or circuit breakex for each elevator per the National <br />Electrical Code with feeder or branch wiring to the controller. Size to suit elevator <br />contractor. <br /> <br />Provide a 120 volt AC, 15 amp, single-phase power supply with fused SPST disconnect <br />switch for each elevator, with feeder wiring to each eonlxoller for ear lights. <br /> <br />Provide a safe and dry on-site storage area l~or elevator material. <br /> <br />Page 10 <br /> <br /> <br />