Laserfiche WebLink
- CITY OF SANTA ANA <br /> III. Overspeed Governors, Governor Tension Sheave Assemblies, and Car and <br /> Counterweight Safeties <br /> iv. Limit, Landing and Slowing Switches <br /> v. Door Protective devices and Alarm Bells <br /> 1. Conduct a yearly no-load low speed test of car and counterweight safeties and a test of <br /> buffers. <br /> j. Periodically equalize the tension in all hoistway ropes. Replace all wire ropes and <br /> fastenings, when conditions warrant. <br /> k. Examine and when conditions warrant, regroove or replace all sheaves, governor tension <br /> sheaves, secondary or deflection sheaves, and compensation sheaves, <br /> I. Periodically examine, lubricate, adjust and when conditions warrant through normal wear <br /> and tear, repair or replace the following accessory equipment: <br /> i. Car and Corridor Operating Push-buttons <br /> ii. Load Weighing Equipment <br /> M. All Wall Lanterns; Car positions, and Hall Position Indicators, Lobby Control <br /> Panels, Car Operation Panels, and all other Signal and Accessory Facilities <br /> furnished and installed as part of the whole equipment. <br /> m. Periodically clean all elevator machine roams, secondary areas, elevator hoistways, and <br /> pit areas. Contractor will be responsible for keeping the machine rooms, the exterior of the <br /> machinery, and any other parts of the equipment subject to rust, properly painted, <br /> identified, and presented to all times. Curing the course of each examination, all <br /> accumulated refuse in the pit areas will be discarded. <br /> n. Annual clean the elevator hoistway and related equipment including rails, inductors, <br /> hoistway door hangers and track relating devices,.switches, buffers,oar tops and pit areas. <br /> o. Steel parts cabinets will be maintained in the machine room areas to provide for the orderly <br /> storage of replacement components, <br /> p. perform the following tests on the elevator equipment, <br /> 1. Tests of the car and counterweight safeties,governors, buffers, and all tither safety <br /> devices. <br /> li. The car balance will be checked and the governor set. If required,the governor will <br /> be re-calibrated and sealed for proper tripping speed. <br /> 5, All tests performed on the elevator equipment described herein will be in accordance with the <br /> most recent ANSUASME A17 Code requirements. Written reports of all tests shall be submitted <br /> and reviewed with the City of the property within thirty(30)day following completion of all tests. <br /> 6. Check the group dispatching systems and make necessary tests to lnsure that all circuits and <br /> time settings are properly adjusted, and that the system performs as designed and installed on <br /> an annual basis. <br /> 7. Bi-AnnuaJ testing of the Fireman's Emergency Service operation will be performed to assure <br /> proper operation of the system. <br /> K. EXCLUDED SERVICES <br /> 1. The following items of elevator equipment, hoistway, and machine room enclosures are not <br /> included in this contract. <br /> ELEVATORS-ALL <br /> City of Santa Ana Rf:P No.25-007A Page 26 of 102 <br />